Chapter 4  Operator Control And Display Panel      35 
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA    User Manual 
4.4   UPS Alarm Message List 
Table 4-8 provides the complete list of UPS alarm messages supported for display either on the Records menu 
(historical data) or in the current record window (prevailing data) as described in 4.1.5  Detailed Description Of Menu 
Items
Table 4-8    UPS alarm message list 
Alarm message 
Description 
Rectifier comm. fail 
Internal RS485 communication failure between monitor and rectifier   
Mains volt. abnormal 
Mains Voltage exceeds the upper or lower limit and results in rectifier shutdown. Check the input 
line-to-neutral voltage amplitude of rectifier 
Mains undervoltage 
Mains voltage is undervoltage. Check the input line voltage 
Mains freq. abnormal 
Mains frequency is out of limit range and results in rectifier shutdown. Check the input voltage and 
frequency  
Battery fuse fail 
Battery fuse flowout led to BCB tripping 
Rectifier block 
Rectifier detected faulty. Rectifier shuts down. Battery discharges 
Rectifier overtemp. 
The temperature of heat sink is too high to keep the rectifier running. The UPS can recover 
automatically. Check the environment and ventilation 
Input fuse fail 
Input fuse blowout led to rectifier turning off 
Control power 1 fail 
UPS operates but Control Power is not available 
Control power 2 fail 
UPS operates but Redundant Control Power is not available 
Mains phase reversed 
Rectifier AC input phase sequence is reversed 
Rectifier current limit 
Rectifier overcurrent led to power limiting operating 
Soft start fail 
Rectifier could not start due to low DC bus voltage   
Input filter fault 
Filter inductor overtemperature led to filter contactor tripping 
Filter contactor fault 
Filter contactor operation abnormal 
Filter overcurrent 
Mains power outside the normal voltage or frequency range of the input passive filter results in filter 
overcurrent. Please find out the reason for the mains power abnormality   
REC drive cirtuit fault 
Rectifier being off due to improper connection of rectifier drive cable or rectifier type setting error 
REC input Ph. missing 
Rectifier input phase missing. Check the input power connection or if the mains power is abnormal 
DC bus over voltage 
Rectifier and inverter were shut down because DC bus voltage is too high. Check whether there is a 
fault in rectifier side 
Bus capacitor overvolt 
Bus capacitor voltage exceeds 350V, rectifier is off. Check the voltages of the two groups of bus 
capacitors 
EPO 
Emergency Power Off direct access key pressed or external command received   
Input disconnect open 
Rectifier input switch open 
Input disconnect closed 
Rectifier input switch closed 
Normal mode 
Load supplied from inverter output through double conversion of the AC mains input supply 
Source share mode 
Load supplied from inverter output through shared double conversion of the AC mains input supply 
and of the Battery supply 
PPF online 
Reactive input filter connected 
PPF disconnecting 
Reactive input filter disconnected 
Battery mode 
Load supplied from inverter output through battery 
No battery 
Check the battery and the battery wiring; check whether the BCB is closed and the BCB dry contact 
is connected   
Auto start 
After UPS was shutdown at EOD, inverter auto starts when utility restore   
Generator connected 
The generator has been connected to the UPS 
BCB open 
Battery Circuit Breaker status (open)   
BCB closed 
Battery Circuit Breaker status (closed)   
Battery float charging     
Battery status (Float charge mode)   
Battery boost charging     
Battery status (Boost charge mode)   
Battery discharging 
Battery status (discharge mode)   
Battery period testing 
Automatic periodic battery maintenance discharge test (20% capacity discharge)   
Batt. capacity testing 
User initiated battery capacity discharge test (100% capacity discharge)   
Batt. maint. testing 
User initiated maintenance discharge test (20% capacity discharge)   
UPS system testing 
User initiated system test 
Inverter in setting 
Inverter starting up and synchronizing   
Rectifier in setting 
Rectifier starting up and synchronizing   
Battery Room Alarm 
Environment in Battery Room Needs Attention