Chapter 4  Operator Control And Display Panel      37 
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA    User Manual 
Alarm message 
Description 
Inverter overtemp. 
The temperature of the inverter heat sink is too high to keep inverter running. This alarm is triggered 
by the signal from a temperature monitoring thermostat on the inverter bridge heat sink. The UPS will 
recover automatically after a 5 minute delay from the disappearance of the overtemperature signal. If 
the overtemperature condition is true, then check for and verify: 1. high ambient air temperature. 2. 
blocked cooling airway. 3. any fan failure. 4. prolonged inverter overload   
Fan fault 
At least one of the cooling fans has failed   
Inverter STS fail 
At least one of the static switches of inverter side is open or short circuit. This fault is locked until 
power off 
Bypass STS fail 
At least one of the static switches of bypass side is open or short circuit. This fault is locked until 
power off   
Operation invalid 
This record is registered following an incorrect operation 
Unit over load 
The UPS is confirmed to be overload when the load arises above 105% nominal rating. The alarm 
automatically resets once the overload condition is removed. 1. Confirm that the alarm is true by 
checking the load percent indicated on the LCD to determine which phase is being overloaded. 2. If 
the alarm is true, measure the actual output current to verify that the indications are valid.   
Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load sharing error 
can also leads to the alarm 
System over load 
The UPS parallel system is confirmed to overload when the total load arises above 105% nominal 
rating for the set basic number of UPSs. The alarm automatically resets once the overload condition 
is removed.   
1. Confirm that the alarm is true by checking the system load percent indicated on the LCD to 
determine which phase is being overloaded. 2. If the alarm is true, measure the actual output current 
to verify that the indications are valid.   
Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load sharing error 
can also leads to the alarm 
Unit over load timeout 
The UPS is confirmed to overload and the overload times out.   
Note 1: the highest loaded phase will indicate overload timing-out first. Note 2: When the timer is 
active then alarm “unit overload” should also be active as the load is above nominal.   
Note 3: When the timer has expired, the inverter Static Switch is opened and the load transferred to 
bypass. The inverter shutdown and will restart after 10 seconds. Note 4: If the load decreases lower 
than 95% after 5 minutes, the system will transfer back to inverter mode.   
Confirm that the alarm is genuine by checking the load percent indicated on the LCD. If an overload 
is indicated then check the load, and investigate any additional load connected prior to the alarm (if 
applicable) 
Byp. abnormal shutdown 
Both bypass and inverter voltages unavailable. Load interruption   
Inverter over current 
Inverter pulse width modulation module overloaded 
Bypass phase reverse 
The phase sequence direction of bypass voltage is reversed. Normally, the phase of phase B lags 
120 degrees behind phase A, and the phase of phase C lags 120 degrees behind phase B.   
Verify that the phase rotation of the bypass supply presented to the UPS is correct, and rectify it if it 
is found to be in error   
Load impact transfer 
A transfer to bypass occurred due to a large step load. The UPS should recover automatically. Turn 
on connected equipment in sequential order to reduce the step loading of the inverter 
Transfer time-out 
The load is on bypass power due to excessive number of transfers that occurred within the last hour. 
The UPS will recover automatically and will transfer the load back to inverter power within an hour 
Load sharing fault 
UPS modules within a parallel system are not sharing the load current equally 
DC bus abnormal 
DC input voltage to inverter beyond limits. Inverter shuts down. Load transfers to bypass 
System transfer 
The whole paralleled UPS system transferred to bypass at the same time. This message will appear 
on the UPS which passive transfer to bypass   
Parallel board fault 
Malfunction of the paralleling control circuits of this UPS module. Can cause system transfer to 
bypass 
Parallel connect fault 
The parallel cables are not connected correctly in a parallel system.   
Reset the fault by pressing the FAULT CLEAR button, then restart the inverter by pressing the 
INVERTER ON button 
Bypass over current 
Bypass current is over limit above 135% rating. The UPS just alarms and does nothing 
LBS Active 
Load Bus Synchronization is active. The UPS is acting as an LBS master or slave in a dual bus 
configuration 
LBS abnormal 
UPS set to LBS mode (master or slave), but no LBS signal on LBS bus. Check the LBS bus 
connection 
Byp. induct overtemp. 
Bypass load sharing inductor overtemperature. Check the environment and ventilation 
Static Sw. overtemp. 
Overtemperature of static switch on bypass or inverter side. Check the environment and ventilation