Chapter 3.  Local Display Menus 
95 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
ambient temperature sensor. Select "None", or the temperature probe (SMTemp8 T8 / ... / 
SMTemp8 T1 / ... / SMTemp1 T8 / ... / SMTemp1 T1 / EIB T2 / EIB T1 / IB2 T2 / IB2 T1). 
You can also select Maximum or Average which takes the maximum or average reading of 
the temperature probes (any of SMTemp8 T8 / ... / SMTemp8 T1 / ... / SMTemp1 T8 / ... / 
SMTemp1 T1 / EIB T2 / EIB T1 / IB2 T2 / IB2 T1) set as ambient temperature probes. 
 
Amb Temp High2: Allows you to set a high ambient temperature alarm 2 point. 
 
Amb Temp High1: Allows you to set a high ambient temperature alarm 1 point. 
 
Amb Temp Low: Allows you to set a low ambient temperature alarm point. 
 
System Temp1: Not used. 
 
System Temp2: Not used. 
 
System Temp3: Not used. 
 
IB2 Temp1: Sets temperature port 1 on the IB2 board to None, Battery, or Ambient. 
 
IB2 Temp2: Sets temperature port 2 on the IB2 board to None, Battery, or Ambient. 
 
EIB Temp1: Sets temperature port 1 on the EIB board to None, Battery, or Ambient. 
 
EIB Temp2: Sets temperature port 2 on the EIB board to None, Battery, or Ambient. 
Note:  You can set High2, High1, and Low temperature alarms for each temperature sensor 
(from the Web Interface). Note that you cannot set high and low temperature alarms for 
individual temperature sensors from the Local Menus. High and low temperature alarm 
settings for the temperature sensors set as ambient are found in the Device Information 
/ Power System / Settings tab. High and low temperature alarm settings for the probes 
set as battery are found in the Device Information / Battery Group / Settings tab. 
Power Split Menu 
See also 
Menu Navigation: Main Menu / Settings / Power System / Power Split 
Note: For WEB Interface; menu items are found under Device Information / Power System / 
Settings Tab. 
"Power Split" Parameter Settings: 
 
Slave Curr Lmt: Current limit point for power system designated as the slave system in a 
"Power Split" configuration. 
 
Delta Volt: The offset voltage that the power system designated as the slave system in a 
"Power Split" configuration is set to. It is suggested to leave this value at the default (0.5 
volts). 
 
Proportion Coeff: The proportional coefficient that the power system designated as the 
slave system in a "Power Split" configuration is set to. It is suggested to leave this value at 
the default (30%). 
 
Integral Time: The integral time that the power system designated as the slave system in 
a "Power Split" configuration is set to. It is suggested to leave this value at the default (60 
seconds). 
Rectifier 
All Rect Set Menu 
Menu Navigation: Main Menu / Settings / Rectifier / All Rect Set 
Note: For WEB Interface; menu items are found under Device Information / Rectifier Group / 
Settings Tab.