"All Rect Set" Parameter Settings: 
 
HVSD: Enables or disables the High Voltage Shutdown feature for all rectifiers. 
 
HVSD Limit: Sets the High Voltage Shutdown point for all rectifiers. 
 
Restart on HVSD: Enables or disables the High Voltage Shutdown Restart feature for all 
rectifiers. 
 
HVSD Restart T: When the High Voltage Shutdown Restart feature is enabled and the 
output exceeds the high voltage limit, the rectifiers restart after this time period expires. 
 
Start Interval: Sets the sequence start interval (time period between starting each rectifier 
in the system). 
 
Walk-In: Enables or disables the start-up walk-in feature for all rectifiers. 
 
Walk-In Time: Sets the walk-in time period for all rectifiers. 
 
Turn On ACOverV: Enables or disables the "Turn On AC Over Voltage" feature. When the 
system is operating on “week” grid input power (i.e. diesel generator), the input voltage 
may have a very high peak voltage which may cause a rectifier not to turn on. If “Turn On 
AC Over Voltage" feature is enabled, the rectifier is forced to turn on. 
 
ECO Mode: Enables or disables the Energy Optimization feature for all rectifiers. When 
enabled, the following parameters can be set. 
 
Best Oper Point: Percent of full load capacity that the rectifiers operate under in the 
Energy Optimization mode. 
 
Fluct Range: If load fluctuation is less than this value, rectifiers are not turned on or off 
for Energy Optimization. 
 
Energy Save Pt: Energy Optimization is disabled if the load is greater than this setting. 
 
Cycle Period: This is the time period that rectifiers are turned on and off to maintain an 
equal operating time for all rectifiers in the system. 
 
Rects ON Time: Time all rectifiers are turned on at End of Cycle. 
 
Turn Off Delay: When the Energy Optimization feature determines a rectifier can be 
switched off, this is the time delay before the rectifier is switched off. 
 
Input Curr Lmt: Sets the Input Current Limit point for all rectifiers. 
 
MixHE Power: Allows the system to use rectifiers of different output capacity. When set to 
derated power, the output capacity of the higher capacity rectifiers are set to the capacity of 
the lowest. 
 
DG Pwr Lmt: Enables or disables the Diesel Power Limit feature. This feature limits 
rectifier output power to a percentage of maximum when AC input is supplied by a 
diesel-alternator set.  
 
Diesel DI Input: Designates which digital input controls operation of the Diesel Power 
Limit feature. 
 
DG Pwr Lmt Pt: Sets, as a percentage, the maximum output power at which rectifiers 
can operate when: 1. the Diesel Power Limit feature is enabled and 2. a digital input 
signal is received from the connected diesel-alternator set. 
 
Current Limit: Enables or disables output current limit. 
 
Current Limit Pt: Sets the output current limit point. 
Rect #1 Menu 
Menu Navigation: Main Menu / Settings / Rectifier / Rect #1 
Note: For WEB Interface; menu items are found under Device Information / Rectifier Group / 