Chapter 2.  Operation 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
Table 4 
Full Alarm Name - WEB 
(Abbreviated 
Alarm Name - LCD) 
Alarm Description 
Action to Correct 
Fuel Tank Config Error 
(Fuel Config Err) 
Fuel tank configuration error. 
-- 
SM Temp Group (SM-Temp Module must be present in system) 
(SM Temp Group) 
SM Temp Lost 
(SMTemp Lost) 
SM-Temp cannot be detected by the 
Controller. 
Reset the SMTemp Lost alarm. 
Replace defective SM-Temp. 
SM Temp 1-8 (SM-Temp Module must be present in system) 
(SMTemp 1-8) 
Communication Interrupt 
(Comm Interrupt) 
SM-Temp has lost communications 
with the Controller. 
Check communications cables. 
Temperature Probe 1 Shorted 
(Probe1 Short) 
Probe shorted. 
Replace temperature probe. 
… 
… 
Temperature Probe 8 Shorted 
(Probe8 Short) 
Probe shorted. 
Temperature Probe 1 Open 
(Probe1 Open) 
Probe open. 
Replace temperature probe. 
… 
… 
Temperature Probe 8 Open 
(Probe8 Open) 
Probe open. 
Table 4 
Available Alarms