2.7 
Power Split Feature 
In Power Split applications, the output of the power system controlled by the ACU+ can be connected in 
parallel with an existing power system. Each system is controlled independently via its own Controller. 
The ACU+ power system is referred to as the "slave" system and the existing power system as the 
"master" system. The Power Split feature controls the ACU+ power system’s output voltage and rectifiers' 
current limit so that the "slave" power system shares the load with the "master" system. 
Optional Functions: The ACU+ Controller 
can mimic the equalize and battery test functions of the “master” 
system’s Controller. In addition, the ACU+ Controller can mimic the low voltage load disconnect and/or 
low voltage battery disconnect functions of the “master” system. This is accomplished by supplying digital 
signals from the 
“master” system’s Controller to the ACU+. This allows these functions to remain active in 
the “master” system. 
2.7.1 
Overview 
See 
2.7.2 
How Power Split Works 
There are four User adjustable parameters for Power Split.  They are: 
 
Slave Curr Lmt: Current limit point for power system designated as the slave system in a "Power 
Split" configuration. 
 
Delta Volt: The offset voltage that the power system designated as the slave system in a "Power 
Split" configuration is set to. It is suggested to leave this value at the default (0.5 volts). 
 
Proportion Coeff: The proportional coefficient that the power system designated as the slave system 
in a "Power Split" configuration is set to. It is suggested to leave this value at the default (30%). 
 
Integral Time: The integral time that the power system designated as the slave system in a "Power 
Split" configuration is set to. It is suggested to leave this value at the default (60 seconds). 
The ACU+ Controller uses these parameters to control the load sharing operation between the two power 
systems. 
Depending on the systems’ configurations, their rectifier capacities, their distribution load capacities, and 
the Power Split configuration; four operating modes can occur. 
Low Load Operation 
When the total load current demand is lower than the SLAVE CURRENT LIMIT value, the ACU+ power 
system voltage will be increased by the programmed DELTA VOLTAGE setting forcing the ACU+ power 
system to carry the load. Make sure that the output voltage does not exceed the battery float range 
recommended by the manufacturer. In this operating mode, no current will be delivered by the existing 
power system. 
Normal Load Operation 
When the total load current demand reaches the SLAVE CURRENT LIMIT value, the ACU+ power 
system operates in output current limit and its output voltage will be decreased (up to the DELTA 
VOLTAGE setting) in order to regulate the current, allowing the existing power system to deliver the 
remaining current. Both the ACU+ power system and the existing power system are now providing current 
to the load. 
High Load Operation 
If current demand increases and the existing power system reaches its current limit setting, float voltage 
will again begin to decrease. When the voltage falls below the float setting minus the DELTA VOLTAGE 
setting, the ACU+ system will come out of current limit and now deliver the additional current necessary to 
satisfy the load. This operation may occur when the batteries are being recharged, such as after a 
commercial AC failure.