Cable Installation
15
6.7
Input and Output Wiring
To connect the input wiring:
1. Locate the input wiring access (see 
illustration at right).
2. Remove the knockout and pull the three/four 
input wires through it, allowing some slack 
for installation.
3. Secure the conduit to the rear panel of the 
Maintenance Bypass Cabinet.
4. Input power cables connect to hex terminals 
on the input terminal block.
5. Insert the ground (earth) wire through the 
earth lug and tighten it to the proper torque 
value (120 in-lb). Then connect the wires to 
the block connections as shown at right. Using 
a torque wrench, turn the screws clockwise 
until tightened to the proper torque value 
(50 in-lb).
NOTE
Input wiring must be installed using conduit.
208 input voltage jumper—if only the connections for 208 VAC are made between the UPS and 
theNfinity Maintenance Bypass, the 208 input voltage jumper must be installed for proper 
operation. To install this jumper, place the jumper wire provided in the accessory kit between 
Pin 1 and Pin 2 on TB4.
NOTE
The Nfinity UPS and Maintenance 
Bypass with transformer contain an 
isolation transformer that generates a 
neutral conductor for the connected 
equipment. The UPS and Maintenance 
Bypass with transformer are a separately 
derived source and contain a
neutral-to-ground bonding jumper. A 
grounding electrode conductor (GEC) 
must be installed in accordance with 
national and local wiring codes and 
regulations.
Input
Conduit
RIGHT HAND OPTION
( LOOKING FROM FRONT OF UNIT )
REAR VIEW
LEFT HAND OPTION
( LOOKING FROM FRONT OF UNIT )
REAR VIEW