Emerson GXT 10KVA Manuel D’Utilisation

Page de 32
Cable Installation
17
Figure 10 Electrical connections—non-transformer model MBC
120V
120V
208V
240V
Common Ground
Wire Connection Torque 
Value: 13 in-lbs
Common Ground
Wire Connection Torque 
Value: 120 in-lbs
Common Ground
Wire Connection Torque 
Value: 120 in-lbs
Common Ground
Wire Connection
Torque Value: 120 in-lbs
TB4 UPS Output Terminal 
Block
Wire Connection Torque 
Value: 28 in-lbs
TB3 UPS Input Terminal 
Block
Wire Connection Torque 
Value: 28 in-lbs
TB5 Hardwire Output Terminal 
Block
Wire Connection Torque
Value: 35 in-lbs
Wire Connection Torque
Value: 120 in-lbs
TB2 Maintenance Bypass 
Terminal Block
Wire Connection Torque 
Value: 50 in-lbs
TB1 Maintenance Bypass Terminal 
Block
Wire Connection Torque
Value: 50 in-lbs