Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
108
Subfeed 64
Subfeed Current Ix
35879
1
A AC
Subfeed Current Iy
35880
1
A AC
Subfeed Current Iz
35881
1
A AC
Subfeed Neutral Current
35882
1
A AC
Subfeed Ground Current
35883
1
10
A AC
Subfeed Output Power (kVA)
35884
1
kVA
Subfeed Output Power (kW)
35885
1
kW
Subfeed Output kW-Hrs
35886
45886
2
10
kWH
Subfeed Power Factor
35888
1
100
Subfeed Output Percent Load
35889
1
-
%
Subfeed Current Ix THD
35890
1
10
%
Subfeed Current Iy THD
35891
1
10
%
Subfeed Current Iz THD
35892
1
10
%
Subfeed Current Ix Crest Factor
35893
1
10
Subfeed Current Iy Crest Factor
35894
1
10
Subfeed Current Iz Crest Factor
35895
1
10
System
System Status
35899
1
1 = Normal Operation
2 = Startup
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
System Event Acknowledge/Reset
45900
1
2 = Reset
4 = Acknowledge
System Date and Time
39998
49998
2
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 36
Liebert FDC
, Liebert FPC
, Liebert RDC
, Liebert RX
 - Input and Holding (continued)
Controller
Liebert iCOM
®
 v4
Liebert Products
Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg.
Scale 
Notes / Units