Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
108
Subfeed 64
Subfeed Current Ix
Subfeed Current Ix
35879
—
1
—
A AC
Subfeed Current Iy
35880
—
1
—
A AC
Subfeed Current Iz
35881
—
1
—
A AC
Subfeed Neutral Current
35882
—
1
—
A AC
Subfeed Ground Current
35883
—
1
10
A AC
Subfeed Output Power (kVA)
35884
—
1
—
kVA
Subfeed Output Power (kW)
35885
—
1
—
kW
Subfeed Output kW-Hrs
35886
45886
2
10
kWH
Subfeed Power Factor
35888
—
1
100
—
Subfeed Output Percent Load
35889
—
1
-
%
Subfeed Current Ix THD
35890
—
1
10
%
Subfeed Current Iy THD
35891
—
1
10
%
Subfeed Current Iz THD
35892
—
1
10
%
Subfeed Current Ix Crest Factor
35893
—
1
10
—
Subfeed Current Iy Crest Factor
35894
—
1
10
—
Subfeed Current Iz Crest Factor
35895
—
1
10
—
System
System Status
35899
—
1
—
1 = Normal Operation
2 = Startup
8 = Normal with Warning
16 = Normal with Alarm
32 = Abnormal Operation
System Event Acknowledge/Reset
—
45900
1
—
2 = Reset
4 = Acknowledge
System Date and Time
39998
49998
2
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 36
Liebert FDC
™
, Liebert FPC
™
, Liebert RDC
™
, Liebert RX
™
- Input and Holding (continued)
Controller
Liebert iCOM
®
v4
Liebert Products
Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units