Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
109
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Table 37
Liebert FDC
, Liebert FPC
, Liebert RDC
, Liebert RX
 - Glossary
Data Label
Data Description
Branch Current Phase 1
Branch breaker Phase 1 RMS current
Branch Current Phase 2
Branch Breaker Phase 2 RMS current
Branch Current Phase 3
Branch breaker Phase 3 RMS current
Branch Output Percent Load
Branch breaker percent load of rated current
Branch Output Power (W)
Branch breaker W
Branch Output Power Factor
Branch breaker Power Factor (real power/apparent power)
Branch Overcurrent
Branch breaker current has exceeded the limit.
Branch Undercurrent Warning
Branch breaker current is less than the limit.
Breaker position
Panelboard pole position of the branch breaker. First position if 2 or 3 pole breaker
Columns of Breakers
The breakers in this panel are physically arranged in this many columns.
Equipment Temperature Sensor Fail
Transformer temperature sensor has failed
Event State
Alarm present
Frequency Deviation
The output frequency is outside a specified range.
Ground Current
Unit Ground RMS current.
Ground Overcurrent
Unit ground current has exceeded the limit.
Input Voltage A-B
Unit Input RMS Voltage between Phase A and Phase B
Input Voltage B-C
Unit Input RMS Voltage between Phase B and Phase C
Input Voltage C-A
Unit Input RMS Voltage between Phase C and Phase A
Neutral Overcurrent
Unit neutral current has exceeded the limit.
Number of Breakers
Number of Breakers in this panelboard.
Output Current Ix Crest Factor
Unit phase X Current Crest Factor (peak/RMS).
Output Current Ix K-Factor
Unit output Current Harmonic K-Factor for phase X.
Output Current Ix THD
Unit Current Total Harmonic Distortion for phase X.
Output Current Ix
Unit Phase X output RMS current.
Output Current Iy Crest Factor
Unit phase Y Current Crest Factor (peak/RMS).
Output Current Iy K-Factor
Unit output Current Harmonic K-Factor for phase Y.
Output Current Iy THD
Unit Current Total Harmonic Distortion for phase Y.
Output Current Iy
Unit Phase Y output RMS current.
Output Current Iz Crest Factor
Unit phase Z Current Crest Factor (peak/RMS).
Output Current Iz K-Factor
Unit output Current Harmonic K-Factor for phase Z.
Output Current Iz THD
Unit Current Total Harmonic Distortion for phase Z.
Output Current Iz
Unit Phase Z output RMS current.
Output Frequency
The system output frequency.
Output kW-Hrs
Branch Breaker accumulated KW-Hours since last KW-Hours reset.
Output kW-Hrs
Unit accumulated KW-Hours since last KW-Hours reset.
Output Neutral Current
Unit output Neutral RMS current.
Output Overcurrent
Unit phase current has exceeded the limit.
Output Overvoltage
Unit voltage has exceeded the limit.
Output Percent Load
Unit percent load of rated current
Output Power (kVA)
Unit output kVA
Output Power (kW)
Unit output KW
Output Power Factor
Unit output Power Factor (real power/apparent power)
Output Undervoltage
Unit voltage is less than the limit.