Modbus 485 and Modbus IP Protocols - UPS Systems
139
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Table 50
Liebert Nfinity
®
 - Status and Coil
Data Description
Status
Coil
Number
of Bits
Scale
Notes / Units
Automatic Battery Test Enabled
10003
3
1
Battery Charger On
10044
1
Inverter Ready
10047
1
Power Factor Correction State
10050
1
Load on Inverter
10073
1
Bypass Active
10074
1
Replace Battery
10081
1
Battery Under Test
10082
1
Load on Battery
10128
1
Load on Bypass
10129
1
Load on Manual Bypass
10132
1
Load Transferred to Bypass Due to UPS Fault
10134
1
Transfer Inhibit
10146
1
Output Off Pending
10151
1
Low Battery - Shutdown Imminent
10152
1
Output Overload
10154
1
UPS Overload
10155
1
Output Off
10158
1
Check Air Filter - Replace
10170
1
Transformer Over Temperature
10178
1
Input Power Supply Fail
10186
1
Internal Device Communication Failure
10284
1
Device Active Alarm
10290
1
Main Control Warning
10291
1
Redundant Control Warning
10292
1
Control Module Failure
10293
1
Redundant Control Module Failed
10294
1
User Interface Module Failed
10295
1
UPS Power Not Redundant
10296
1
Power Module Failure
10298
1
Battery Module Failure
10299
1
Power Module Warning
10300
1
Battery Module Warning
10301
1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.