Emerson MODBUS IP Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - Thermal Management Products
11
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Remote Sensor Over Temperature 6
10361
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Over Temperature 7
10362
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Over Temperature 8
10363
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Over Temperature 9
10364
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Over Temperature 10
10365
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Under Temperature 1
10366
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Under Temperature 2
10367
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Under Temperature 3
10368
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Under Temperature 4
10369
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Under Temperature 5
10370
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Under Temperature 6
10371
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Under Temperature 7
10372
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Under Temperature 8
10373
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Under Temperature 9
10374
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Under Temperature 10
10375
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Issue 1
10376
 —
1
Active on Alarm
1, 2, 3, 4, 5, 6
Remote Sensor Issue 2
10377
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Issue 3
10378
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Issue 4
10379
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Issue 5
10380
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Issue 6
10381
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Issue 7
10382
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Issue 8
10383
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Issue 9
10384
 —
1
Active on Alarm
2, 3, 4, 5, 6
Remote Sensor Issue 10
10385
 —
1
Active on Alarm
2, 3, 4, 5, 6
Air Economizer Emergency Override
10386
 —
1
Active on Alarm
2, 3, 4, 5, 6
Air Economizer Reduced Airflow
10387
 —
1
Active on Alarm
2, 3, 4, 5, 6
Temperature Control Sensor Issue
10388
 —
1
Active on Alarm
2, 3, 4, 5, 6
EEV Unspecified General Event
10488
 —
1
Active on Alarm
4, 5
Static Pressure Sensor Issue
10489
 —
1
Active on Alarm
3, 5, 6
High Static Pressure
10490
 —
1
Active on Alarm
3, 5, 6
Low Static Pressure
10491
 —
1
Active on Alarm
3, 5, 6
Pump Unspecified General Event
10492
 —
1
Active on Alarm
4, 5
Condenser Unit Unspecified General Event
10493
 —
1
Active on Alarm
3, 4, 5, 6
Table 6
Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
 - Status and Coil (continued)
Controller
Liebert iCOM
®
 v4
Liebert Products
Units with 
Liebert iCOM
®
:
Liebert HPM
Units with Liebert iCOM Firmware
PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe System/3
Liebert DS
Liebert DSE
Liebert PeX
Available Points
Data Label
Status
Coil
Number
of Bits
Notes / Units
Extra Notes