Emerson MODBUS IP Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - Thermal Management Products
13
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Table 8
Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
 - Input and Holding
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale
Notes / Units
Extra
Notes
Free Cooling Internal Control Mode
30017
40017
1
 —
0 = Disabled
1 = Contact
2 = Value
1
Humidity Proportional Control Type
30018
40018
1
 —
0 = Relative
1 = Compensated
2 = Predictive
1
Fan Speed Maximum Set Point
30019
40019
1
 —
%
1, 2, 3, 4, 5, 6
Supply Air Temperature Set Point
30020
40020
1
 —
deg C
1
Supply Air Temperature Set Point
30733
40733
1
 —
deg F
1
Free Cooling Internal Temperature Delta
30021
40021
1
10
deg C
1, 2, 3, 4, 5, 6
Free Cooling Internal Temperature Delta
30734
40734
1
10
deg F
1, 2, 3, 4, 5, 6
Minimum Chilled Water Temp Set Point
30022
40022
1
10
deg C
1, 2, 3, 4, 5, 6
Minimum Chilled Water Temp Set Point
30735
40735
1
10
deg F
1, 2, 3, 4, 5, 6
Air Temperature Set Point
30023
40023
1
10
deg C
1, 2, 3, 4, 5, 6
Air Temperature Set Point
30736
40736
1
10
deg F
1, 2, 3, 4, 5, 6
Air Temperature Proportional Band
30024
40024
1
10
deg C
1, 2, 3, 4, 5, 6
Air Temperature Proportional Band
30737
40737
1
10
deg F
1, 2, 3, 4, 5, 6
Air Temperature Dead Band
30025
40025
1
10
deg C
1, 2, 3, 4, 5, 6
Air Temperature Dead Band
30738
40738
1
10
deg F
1, 2, 3, 4, 5, 6
Air Temperature Control Integration Time
30026
40026
1
10
min
1, 2, 3, 4, 5, 6
Humidity Set Point
30027
40027
1
 —
% RH
1, 2, 3, 4, 5, 6
Humidity Proportional Band
30028
40028
1
 —
% RH
1, 2, 3, 4, 5, 6
Humidity Proportional Control Integration 
Time
30029
40029
1
10
min
1, 2, 3, 4, 5, 6
Humidity Dead Band
30030
40030
1
10
% RH
1, 2, 3, 4, 5, 6
Auto Restart Delay
30031
40031
1
 —
sec
1, 2, 3, 4, 5, 6
Air Temperature Control Type
30033
40033
1
 —
0 = Proportional
1 = Prop+Integral
3 = Intelligent
1, 2, 3, 4, 5, 6
BMS Timeout Period
30045
40045
1
 —
min
1, 2, 3, 4, 5, 6
Return Air Over Temp Threshold
30050
40050
1
10
deg C
1, 2, 3, 4, 5, 6
Return Air Over Temp Threshold
30739
40739
1
10
deg F
1, 2, 3, 4, 5, 6
Return Air Under Temp Threshold
30051
40051
1
10
deg C
1, 2, 3, 4, 5, 6
Return Air Under Temp Threshold
30740
40740
1
10
deg F
1, 2, 3, 4, 5, 6
Ext Air Sensor A Over Temp Threshold
30052
40052
1
10
deg C
1, 2, 3, 4, 5, 6
Ext Air Sensor A Over Temp Threshold
30741
40741
1
10
deg F
1, 2, 3, 4, 5, 6
Ext Air Sensor A Under Temp Threshold
30053
40053
1
10
deg C
1, 2, 3, 4, 5, 6
Ext Air Sensor A Under Temp Threshold
30742
40742
1
10
deg F
1, 2, 3, 4, 5, 6
High Return Humidity Threshold
30054
40054
1
10
% RH
1, 2, 3, 4, 5, 6
Low Return Humidity Threshold
30055
40055
1
10
% RH
1, 2, 3, 4, 5, 6
Ext Air Sensor A High Humidity Threshold
30056
40056
1
10
% RH
1, 2, 3, 4, 5, 6
Ext Air Sensor A Low Humidity Threshold
30057
40057
1
10
% RH
1, 2, 3, 4, 5, 6
Fan Hours Threshold
30070
40070
1
 —
hr
1, 2, 3, 4, 5, 6