Emerson MODBUS IP Manuel D’Utilisation
Modbus 485 and Modbus IP Protocols - Thermal Management Products
15
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Dig Scroll Comp Discharge Temp 2
30751
—
1
—
deg F
1, 2, 3, 4, 5, 6
Return Humidity
30130
—
1
10
% RH
1, 2, 3, 4, 5, 6
Ext Air Sensor A Humidity
30132
—
1
10
% RH
1, 2, 3, 4, 5, 6
Ext Air Sensor B Humidity
30133
—
1
10
% RH
1, 2, 3, 4, 5, 6
Ext Air Sensor C Humidity
30134
—
1
10
% RH
1, 2, 3, 4, 5, 6
Fan Hours
30141
40141
1
—
hr
1, 2, 3, 4, 5, 6
Compressor Hours 1
30142
40142
1
—
hr
1, 2, 3, 4, 5, 6
Compressor Hours 2
30143
40143
1
—
hr
1, 2, 3, 4, 5, 6
Humidifier Hours
30144
40144
1
—
hr
1, 2, 3, 4, 5, 6
Dehumidifier Hours
30145
40145
1
—
hr
1, 2, 3, 4, 5, 6
Free Cooling Valve Hours
30146
40146
1
—
hr
1, 2, 3, 4, 5, 6
Electric Reheater Hours 1
30147
40147
1
—
hr
1, 2, 3, 4, 5, 6
Electric Reheater Hours 2
30148
40148
1
—
hr
1, 2, 3, 4, 5, 6
Electric Reheater Hours 3
30149
40149
1
—
hr
1, 2, 3, 4, 5, 6
Hot Water / Hot Gas Valve Hours
30150
40150
1
—
hr
1, 2, 3, 4, 5, 6
Today's High Air Temperature
30151
—
1
10
deg C
1, 2, 3, 4, 5, 6
Today's High Air Temperature
30752
—
1
10
deg F
1, 2, 3, 4, 5, 6
Today's Low Air Temperature
30153
—
1
10
deg C
1, 2, 3, 4, 5, 6
Today's Low Air Temperature
30753
—
1
10
deg F
1, 2, 3, 4, 5, 6
Today's High Humidity
30155
—
1
10
% RH
1, 2, 3, 4, 5, 6
Today's Low Humidity
30157
—
1
10
% RH
1, 2, 3, 4, 5, 6
Server Class
30257
—
1
—
1 = UPS
2 = AIR
3 = PMP
4 = PDU
1, 2, 3, 4, 5, 6
Today's High Air Temperature Time
30258
—
2
-
Seconds since Midnight
1, 2, 3, 4, 5, 6
Today's Low Air Temperature Time
30260
—
2
-
Seconds since Midnight
1, 2, 3, 4, 5, 6
Supply Air Temperature Sensor Control
30262
40262
1
—
0 = Disabled
1 = Limit
2 = Control
3 = Temp Only
1
Return Air Temperature Set Point
30263
40263
1
—
deg C
1
Return Air Temperature Set Point
30754
40754
1
—
deg F
1
Return Humidity Set Point
30264
40264
1
—
% RH
1
Today's High Humidity Time
30265
—
2
—
Seconds since Midnight
1, 2, 3, 4, 5, 6
Today's Low Humidity Time
30267
—
2
—
Seconds since Midnight
1, 2, 3, 4, 5, 6
Fixed Compressor State 1
30269
—
1
—
0 = off
1 = on
1, 2, 3, 4, 5, 6
Fixed Compressor State 2
30270
—
1
—
0 = off
1 = on
1, 2, 3, 4, 5, 6
Compressor Capacity Control State 1
30271
—
1
—
0 = off
1 = on
1, 2, 3, 4, 5, 6
Compressor Capacity Control State 2
30272
—
1
—
0 = off
1 = on
1, 2, 3, 4, 5, 6
Table 8
Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale
Notes / Units
Extra