Emerson MODBUS IP Manuel D’Utilisation

Page de 372
BACnet Communications - UPS Systems
343
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Rectifier
Rectifier Failure
Binary_Value
160
4295_1
RD
Active on Alarm
Vdc Backfeed
Binary_Value
162
5879_1
RD
Active on Alarm
Rectifier Configuration Change Request
Binary_Value
163
5880_1
RD
Active on Alarm
System
System Fan Failure - Redundant
Binary_Value
174
4749_1
RD
Active on Alarm
Multiple Fan Failure
Binary_Value
175
4750_1
RD
Active on Alarm
Internal Communications Failure
Binary_Value
176
4300_1
RD
Active on Alarm
UPS Output on Bypass
Binary_Value
177
4298_1
RD
Active on Alarm
Output Load on Maint. Bypass
Binary_Value
178
4299_1
RD
Active on Alarm
Backfeed Breaker Open
Binary_Value
179
4325_1
RD
Active on Alarm
Auto Restart In Progress
Binary_Value
180
4316_1
RD
Active on Alarm
Power Supply Failure
Binary_Value
181
4314_1
RD
Active on Alarm
Auto Restart Inhibited - Ext
Binary_Value
183
4317_1
RD
Active on Alarm
Automatic Restart Failed
Binary_Value
184
4439_1
RD
Active on Alarm
Main Controller Fault
Binary_Value
185
4753_1
RD
Active on Alarm
Fuse Failure
Binary_Value
186
4440_1
RD
Active on Alarm
System Controller Error
Binary_Value
187
4441_1
RD
Active on Alarm
System Breaker(s) Open Failure
Binary_Value
188
4442_1
RD
Active on Alarm
System Breaker(s) Close Failure
Binary_Value
189
4754_1
RD
Active on Alarm
Input Filter Cycle Lock
Binary_Value
190
4755_1
RD
Active on Alarm
EMO Shutdown
Binary_Value
191
5769_1
RD
Active on Alarm
Service Code Active
Binary_Value
192
4756_1
RD
Active on Alarm
LBS Active
Binary_Value
193
4757_1
RD
Active on Alarm
LBS Inhibited
Binary_Value
194
4758_1
RD
Active on Alarm
Regeneration Active
Binary_Value
195
5881_1
RD
Active on Alarm
Regeneration Operation Terminated
Binary_Value
196
5882_1
RD
Active on Alarm
Regeneration Operation Failure
Binary_Value
197
5883_1
RD
Active on Alarm
Leading Power Factor
Binary_Value
198
4759_1
RD
Active on Alarm
Controls Reset Required
Binary_Value
199
4760_1
RD
Active on Alarm
MultiModule
Loss of Redundancy
Binary_Value
212
4825_1
RD
Active on Alarm
MMS Overload
Binary_Value
215
4831_1
RD
Active on Alarm
MMS On Battery
Binary_Value
216
4834_1
RD
Active on Alarm
MMS Module Alarm Active
Binary_Value
218
5145_1
RD
Active on Alarm
Program Input Signals
Program Input Contact 01
Binary_Value
229
5884_1
RD
Active on Alarm
Program Input Contact 02
Binary_Value
230
5885_1
RD
Active on Alarm
Program Input Contact 03
Binary_Value
231
5886_1
RD
Active on Alarm
Program Input Contact 04
Binary_Value
232
5887_1
RD
Active on Alarm
Program Input Contact 05
Binary_Value
233
5888_1
RD
Active on Alarm
Program Input Contact 06
Binary_Value
234
5889_1
RD
Active on Alarm
Program Input Contact 07
Binary_Value
235
5890_1
RD
Active on Alarm
Program Input Contact 08
Binary_Value
236
5891_1
RD
Active on Alarm
Table 110 Liebert NXL
 - 50 Hz, CE version (Models 48 and 49)—Binary Data
Data Label
Object
Type
Instance
Object
Name
Access
Notes