Emerson MODBUS IP Manuel D’Utilisation

Page de 372
BACnet Communications - UPS Systems
341
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Table 110 Liebert NXL
 - 50 Hz, CE version (Models 48 and 49)—Binary Data
Data Label
Object
Type
Instance
Object
Name
Access
Notes
Input
System Input Power Problem
Binary_Value
1
4122_1
RD
Active on Alarm
System Input Phs Rotation Error
Binary_Value
2
4146_1
RD
Active on Alarm
System Input Current Limit
Binary_Value
3
4147_1
RD
Active on Alarm
System Input Current Imbalance
Binary_Value
4
4382_1
RD
Active on Alarm
Bypass
Bypass Not Available
Binary_Value
15
4135_1
RD
Active on Alarm
Bypass Overload Phase A
Binary_Value
16
4132_1
RD
Active on Alarm
Bypass Overload Phase B
Binary_Value
17
4133_1
RD
Active on Alarm
Bypass Overload Phase C
Binary_Value
18
4134_1
RD
Active on Alarm
Bypass Auto Retransfer Failed
Binary_Value
19
4138_1
RD
Active on Alarm
Bypass Static Switch Overload
Binary_Value
20
4142_1
RD
Active on Alarm
Bypass Static Switch Unavailable
Binary_Value
21
4143_1
RD
Active on Alarm
Bypass Auto Transfer Failed
Binary_Value
22
4145_1
RD
Active on Alarm
Bypass Frequency Error
Binary_Value
23
4175_1
RD
Active on Alarm
Bypass - Manual Rexfr Inhibited
Binary_Value
24
4218_1
RD
Active on Alarm
Bypass - Manual Xfr Inhibited
Binary_Value
25
4217_1
RD
Active on Alarm
Battery
Battery Automatic Test Inhibited
Binary_Value
36
4740_1
RD
Active on Alarm
Battery Capacity Low
Binary_Value
37
4166_1
RD
Active on Alarm
Battery Discharging
Binary_Value
38
4168_1
RD
Active on Alarm
Battery Temperature Imbalance
Binary_Value
39
4169_1
RD
Active on Alarm
Battery Equalize
Binary_Value
40
4170_1
RD
Active on Alarm
Battery Auto Test In Progress
Binary_Value
41
4172_1
RD
Active on Alarm
Main Battery Disconnect Open
Binary_Value
42
4173_1
RD
Active on Alarm
Battery Low
Binary_Value
43
4162_1
RD
Active on Alarm
Battery Temperature Sensor Fault
Binary_Value
44
4174_1
RD
Active on Alarm
Battery Circuit Breaker 1 Open
Binary_Value
45
4176_1
RD
Active on Alarm
Battery Circuit Breaker 2 Open
Binary_Value
46
4179_1
RD
Active on Alarm
Battery Circuit Breaker 3 Open
Binary_Value
47
4182_1
RD
Active on Alarm
Battery Circuit Breaker 4 Open
Binary_Value
48
4185_1
RD
Active on Alarm
Battery Circuit Breaker 5 Open
Binary_Value
49
4188_1
RD
Active on Alarm
Battery Circuit Breaker 6 Open
Binary_Value
50
4191_1
RD
Active on Alarm
Battery - External Monitor 1
Binary_Value
51
4220_1
RD
Active on Alarm
Battery - External Monitor 2
Binary_Value
52
4221_1
RD
Active on Alarm
Battery Ground Fault
Binary_Value
53
4222_1
RD
Active on Alarm
Battery Over Temperature Limit
Binary_Value
54
5871_1
RD
Active on Alarm
Battery Low Shutdown
Binary_Value
55
4742_1
RD
Active on Alarm
Battery Over Temperature
Binary_Value
56
4219_1
RD
Active on Alarm
Battery Test Failed
Binary_Value
57
4323_1
RD
Active on Alarm
Unexpected Main Battery Disconnect Closure
Binary_Value
58
5873_1
RD
Active on Alarm
Battery Over Voltage
Binary_Value
59
5874_1
RD
Active on Alarm
Battery Fuse Fault
Binary_Value
60
5875_1
RD
Active on Alarm
Main Battery Disconnect Forced To Unlock
Binary_Value
61
5878_1
RD