Emerson MODBUS IP Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - Thermal Management Products
49
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Table 14
Liebert HPC
 (Chiller) - Status and Coil
Controller
Liebert iCOM
®
 v4
Data Label
Status
Coil
Number
of Bits
Notes
Extra
Notes
Compressors
Compressor Not Stopping
10001
1
Active on Alarm
1, 2
Compressor Superheat Over Threshold
10002
1
Active on Alarm
2
Compressor 1
Compressor Hours Exceeded
10012
1
Active on Alarm
1, 2
Compressor High Head Pressure
10013
1
Active on Alarm
1, 2
Compressor Low Suction Pressure
10014
1
Active on Alarm
1, 2
Compressor Thermal Overload
10015
1
Active on Alarm
1, 2
Compressor Low Oil Pressure
10016
1
Active on Alarm
1, 2
Compressor Loss of Differential Pressure
10018
1
Active on Alarm
1, 2
Compressor Capacity Reduced
10019
1
Active on Alarm
1, 2
Compressor Capacity Normal
10020
1
Active on Alarm
2
Compressor Contactor Issue
10021
1
Active on Alarm
2
Compressor 2
Compressor Hours Exceeded
10029
1
Active on Alarm
1, 2
Compressor High Head Pressure
10030
1
Active on Alarm
1, 2
Compressor Low Suction Pressure
10031
1
Active on Alarm
1, 2
Compressor Thermal Overload
10032
1
Active on Alarm
1, 2
Compressor Low Suction Pressure
10033
1
Active on Alarm
1, 2
Compressor Loss of Differential Pressure
10035
1
Active on Alarm
1, 2
Compressor Capacity Reduced
10036
1
Active on Alarm
1, 2
Compressor Capacity Normal
10037
1
Active on Alarm
2
Compressor Contactor Issue
10038
1
Active on Alarm
2
Compressor 4
Compressor Hours Exceeded
10230
1
Active on Alarm
1, 2
Compressor High Head Pressure
10231
1
Active on Alarm
1, 2
Compressor Low Suction Pressure
10232
1
Active on Alarm
1, 2
Compressor Thermal Overload
10233
1
Active on Alarm
1, 2
Compressor Low Suction Pressure
10234
1
Active on Alarm
1, 2
Compressor Loss of Differential Pressure
10236
1
Active on Alarm
1, 2
Compressor Capacity Reduced
10237
1
Active on Alarm
1, 2
Compressor Capacity Normal
10238
1
Active on Alarm
2
Compressor Contactor Issue
10239
1
Active on Alarm
2
Condensers 1
Condenser Fan Issue
10046
1
Active on Alarm
1, 2
Low Condenser Refrigerant Pressure
10047
1
Active on Alarm
1, 2
Condenser Max Fan Speed Override
10048
1
Active on Alarm
1, 2
Condensers 2
Condenser Fan Issue
10058
1
Active on Alarm
1, 2
Low Condenser Refrigerant Pressure
10059
1
Active on Alarm
1, 2
Condenser Max Fan Speed Override
10060
1
Active on Alarm
1, 2
Condensers 4
Condenser Fan Issue
10066
1
Active on Alarm
1, 2
Low Condenser Refrigerant Pressure
10067
1
Active on Alarm
1, 2
Condenser Max Fan Speed Override
10068
1
Active on Alarm
1, 2