Chapter 3. Maintenance 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
Rectifiers modules can be installed in any mounting position of each module mounting 
shelf.  Converters modules can be installed in any of the three far right mounting 
positions of each module mounting shelf (as viewed from the front).  See Figure 3-1. 
Note:  Each rectifier and converter module locks into the module mounting shelf by 
means of a latch located on the bottom of the module.  The latch and module 
handle are interactive.  Pushing the handle up into the module’s front panel 
causes the latch to extend to the locking position; pulling the handle down out 
from the module’s front panel causes the latch to retract.  See Figure 3-1.
 
Warning:  To prevent damage to the latching mechanism, ensure the handle is in 
the open position when installing or removing a module.  NEVER hold 
the handle in the closed position when installing a module into a shelf. 
Procedure 
1)  Unpack the modules. 
2)  Note the model number located on the front of each module.  Model numbers 
starting with the letter “R” are rectifier modules.  Model numbers starting with the 
letter “C” are converter modules. 
3)  Place the module into an unoccupied mounting position without sliding it in 
completely.  Rectifiers modules can be installed in any mounting position of each 
module mounting shelf.  Converters modules can be installed in any of the three 
far right mounting positions of each module mounting shelf (as viewed from the 
front).  See Figure 3-1. 
4)  Loosen the 
captive screw on the module’s handle.  Pull the handle down out from 
the module’s front panel (this will also retract the latch mechanism).  See Figure 
3-1.
 
5)  Push the module completely into the shelf. 
6) 
Push the handle up into the module’s front panel.  This will lock the module 
securely to the shelf.  Tighten the captive screw on the handle. 
7)  Repeat the above steps for each module being installed in the system. 
8)  After the modules are physically installed in the mounting shelf(s), they are ready 
for operation immediately after power is supplied to them. 
Note:  It is recommended that the current limit point be checked whenever a rectifier 
is added to or removed from the power system.  
”. 
Note:  The rectifier or converter being added is assigned by the ACU+ the lowest 
available identification number.  If desired, you can change the identification 
number
, see “Configuring the ACU+ Identification of Rectifiers” or 
“Configuring the ACU+ Identification of Converters” in Chapter 5 of the 
separate Power System Installation Manual (IM582127000).