User Instructions 
Issue AC, January 2, 2013 
Spec. No. 582127000 (Model 721
NPBB
 
Page 14 
Chapter 3. Maintenance 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
INSTALLING A FIELD EXPANSION RECTIFIER MODULE 
MOUNTING SHELF SPEC. NO. 588705000 
Danger:  Adhere to the 
“Important Safety Instructions” presented at the front of 
this document. 
Note:  Refer to Figure 3-2 and Figure 3-3 as this procedure is performed. 
Procedure 
1)  Install the expansion rectifier module mounting shelf directly below the bottom-
most rectifier module mounting shelf in the rack.  Use the mounting hardware 
provided in the expansion busbar kit. 
Hardware build-up is: 
12-24 x 3/4" screw and flat washer, (1) set per side. 
 
 
 
 
 
 
12-24 x 3/4" screw and ground washer, (1) set per side. 
Note:  Install the ground washers so the teeth make contact with the metal on 
the mounting angles.  Torque all screws to 65 in-lbs. 
2)  On the rear of the expansion rectifier module mounting shelf and the existing 
shelf installed directly above it, remove the rear shield that covers the output 
busbars. 
Note:  Apply electrical anti-oxidizing compound to busbar mating surfaces before 
performing the next step. 
3)  Secure the 
existing shelf’s busbars to the expansion shelf’s mating busbars with 
the supplied interconnect busbars and hardware. 
Hardware build-up for these connections are: 
 
1/4-20 x 1" bolt, 
 
1/4" Belleville lock washer, 
 
1/4" flat washer. 
Install the Belleville lock washer so the concave side is towards the busbar.  
Torque all connections to 60 in-lbs. 
If installing a second expansion rectifier module mounting shelf, 1/4-20 nuts 
(included) are required in lieu of the 1/4-
20 x 1” bolts (see Figure 3-2)
4)  Disconnect the cable coming from the distribution cabinet from the bottom 
connector on the bottom-most existing rectifier shelf. 
5)  Connect the bottom connector on the bottom-most existing rectifier shelf to the 
top connector on the expansion rectifier shelf. 
6)  Connect the cable disconnected in step 4) (coming from distribution cabinet) to 
the bottom connector on expansion rectifier shelf. 
7)  Replace the rear covers removed in step 2) above. 
8)  Refer to the Power System Installation Instructions (IM582127000) and connect 
AC input power to the expansion shelf. 
9)  Refer to the Rectifier Instructions and install rectifier modules into the expansion 
shelf as required.