List NB:  Distribution Bus Module (P/N 513809) 
(3) GJ/218 Circuit Breaker Battery Disconnect Positions 
Features 
♦  Single Voltage Distribution (+24V) 
♦  500A Maximum Capacity 
♦  (3) Battery Disconnect Circuit Breaker Mounting Positions 
(100 to 600A GJ/218-Type) NOTE RESTRICTIONS 
Restrictions 
Limit one bus arrangement of this type per Distribution Cabinet. 
Must be installed in bus position A or B (row 1 or 2) of a 1-, 2-, 3-, or 4-bus row cabinet. 
Cannot be used in second row of a 3-bus row cabinet in List 1 if used with List 2. 
Cannot be used in second row of a 3-bus row cabinet in List 2. 
Panel is designed to mount circuit breakers in the following possible combinations: 
(3) 100A to 250A 
(1) 100A to 250A and (1) 300A or 400A 
(1) 600A 
Ordering Notes 
1)  Order circuit breakers and associated jumper kits as required per Tables 
2)  Order battery lugs (two hole, 3/8” bolt clearance hole, 1” centers) as required for each distribution position 
per Table 
1"
1"
1"
BATTERY DISCONNECT
BATTERY (LOAD SIDE)
CONNECTIONS
3/8-16 CAPTIVE NUT, 6 PLACES
(CUSTOMER MUST SUPPLY LUG
BOLTS AND ADDITIONAL
HARDWARE.  BOLT LENGTH: 1-1/4")