Emerson SAG581126000 Manuel D’Utilisation

Page de 123
SAG581126000 
System Application Guide 
Issue AD, November 23, 2009 
Spec. No. 581126000 (Model 700
NVBA
 
Page 64 of 123 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
List ND:  Distribution Bus Module (P/N 514030) 
(2) TPH Fuse Battery Disconnect Positions 
Features 
♦  Single Voltage Distribution (+24V) 
♦  960A Maximum Capacity 
♦  (2) Battery Disconnect Fuse Mounting Positions 
(70 to 600A TPH-Type) 
Restrictions 
Limit one bus arrangement of this type per Distribution Cabinet. 
Must be installed in bus position A (row 1) of a 1-, 2-, 3-, or 4-bus row cabinet. 
Ordering Notes 
1)  Order fuses as required pe
.  Order replacement alarm fuses (1/4A) per 
2)  Order battery lugs (two hole, 3/8 bolt clearance hole, 1” centers) as required for each distribution position 
per Table 
1"
BATTERY DISCONNECTS
BATTERY 
(LOAD SIDE) 
CONNECTIONS
BATTERY 
(LOAD SIDE) 
CONNECTIONS
2-1/8"
2-1/8"
2-1/8"
2-1/8"
3/8-16 CAPTIVE NUT, 12 PLACES (CUSTOMER MUST 
SUPPLY LUG BOLTS AND ADDITIONAL HARDWARE.  
BOLT LENGTH: 1-1/4")