Emerson SAG581126000 Manuel D’Utilisation

Page de 123
SAG581126000 
System Application Guide 
Issue AD, November 23, 2009 
Spec. No. 581126000 (Model 700
NVBA
 
Page 76 of 123 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
GJ/218-Type Circuit Breakers 
Restrictions 
A bus arrangement must be specified that contains GJ/218-type circuit breaker positions. 
Load should not exceed 80% of device rating. 
Refer to 
 for required distribution row mounting positions. 
Ordering Notes 
1)  Order circuit breakers as required per 
2)  Order a jumper kit as required for each circuit breaker per 
GJ/218 Circuit Breakers
 
Ampere 
Rating 
Number 
of 
Positions 
P/N 
Electrical/ 
Mechanical Trip
1
 
without 
Internal Shunt 
P/N 
Electrical Trip
2
 
without 
Internal Shunt 
P/N 
Electrical Trip
2
 
with 
Internal Shunt
(25mV @ full 
rated load)
 3
 
P/N 
Electrical/ 
Mechanical Trip
1
 
with 
Internal Shunt 
(25mV @ full 
rated load)
 3
 
for wire size 
and lug 
selection, 
refer to the 
following 
table 
100 1  256621700 
256621300 
516184 
123580 
125 1  256621600 
256621400 
516187 
123631 
150 1  256621800 
256622400 
516185 
123632 
175 1  256621900 
256622500 
516186 
123633 
200 1  256622200 
256622600 
516188 
123634 
225 1  256622900 
256622700 
516189 
123635 
250 1  256623500 
256623400 
516190 
123636 
300 2  256625300  103572 
-- 
-- 
400 2  256626200 
256626300  -- 
-- 
600 3  256628200  103571 
-- 
-- 
1, 2
  Circuit Breaker Alarm Operation: 
1
 
Provides an alarm during an electrical or manual trip condition. 
Provides an alarm during an electrical trip condition only. 
3
 
Extended shunt leads are 22 AWG stranded wire, approximately 7-10 ft. long from exit point at bottom of 
Distribution Cabinet.  Each shunt lead is equipped with a 49.9 ohm current limiting resistor.   
Table 5 
GJ/218 Circuit Breakers