1.3.5 
Battery Management 
General Battery Management 
The ACU+ Controller provides the following battery management functions 
(except Lithium Ion Battery Configuration). 
 
Battery Charge Temperature Compensation 
 
Battery Equalize Charge 
 
Battery Charge Current Limit 
 
High and Low Battery Temperature Alarms 
 
Battery Thermal Runaway Management (BTRM) Feature 
(Reduces Voltage during a High Battery Temperature Condition) 
 
Battery Discharge Tests 
 
Battery Test Logs (maximum twelve [12] logs, maximum eighteen [18] battery strings per log) 
 
Battery LVD (Low Voltage Disconnect) 
 
Battery Capacity Prediction 
 
Battery Block and Battery Midpoint Monitoring 
 
Enhanced Battery Monitoring with SM-BRC 
 
Thermal Runaway Detection/Management 
Spec. No. 588820300 Battery Rack System (Lithium Ion Battery Configuration) 
When the ACU+ is equipped with the Lithium Ion Battery Configuration for use with Spec. No. 588820300 
NetSure
™ Battery Rack System, the battery management functions are as follows. 
 
The configuration only provides the battery float charge voltage (equalize charging is not applicable). 
 
The only adjustable battery setting (besides the float voltage level) is the ABCL (Active Battery 
Charge Current Limit) Point. 
 
Active Battery Charge Current Limit (ABCL):  This feature controls the amount of charge current 
supplied to the lithium-ion batteries installed in the power plant to prevent failure of the batteries. 
 
Battery status and alarms sent by the batteries to the ACU+ are displayed in the ACU+ interfaces. 
 
Refer also to the instructions provided by the battery manufacturer for battery management functions 
built into the battery itself. 
NOTE THAT THE FOLLOWING DESCRIPTIONS ARE FOR THE GENERAL BATTERY 