Emerson M820D Manuel D’Utilisation

Page de 176
UM1M820BNA 
User Instructions 
Issue AH, March 4, 2013 
Spec No. 1M820BNA (Model M820B) 
 
Spec No. 1M820DNA (Model M820D) 
 
Chapter 1.  Introduction 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
Figure 1 illustrates the various methods to interface with the ACU+ Controller remotely. 
 
Figure 1 
ACU+ Remote Communications 
1.3 
Function Descriptions 
1.3.1 
Rectifier Control 
Rectifiers are automatically controlled by the ACU+ Controller. The ACU+ Controller provides an Energy 
Optimization Mode function. Energy Optimization permits an installation to only operate rectifiers as 
needed to maintain the load and keep batteries in a fully charged condition. As load increases, Energy 
Optimization turns on additional rectifiers as needed to maintain the load. As load decreases, Energy 
Optimization places rectifiers in standby to conserve energy usage. Rectifiers which are always operating 
to maintain any load requirements are cycled through the group of rectifiers controlled by this feature to 
provide uniform operating times for each rectifier. 
1.3.2 
Converter Control 
Converters are automatically controlled by the ACU+ Controller.