List LS:  Distribution Cabinet 
(18) Fuse/Circuit Breaker System Positions with 
Load Shunt 
Features 
♦  Single Voltage Distribution (-48V) 
♦  Maximum Capacity:  Input:  500A max. 
Total Distribution:  300A max. 
Battery Recharge Current:  500A max. @ +50°C; 400A @ +65°C. 
Battery Terminals as Remote Feed:  200A max. 
♦  (18) Mounting Positions for Load Distribution Fuses or Circuit Breakers, or accepts 
♦  Accepts TPS/TLS-Type Fuses (3 to 100A) or Bullet Nose Type Circuit Breakers (1 to 100A) 
Caution:  A circuit breaker or fuse with a rating greater than 75 amperes SHALL HAVE an empty 
mounting position between it and any other overcurrent protective device. 
Caution:  The maximum size circuit breaker or fuse used in ambient temperatures above +50°C 
ambient shall be 40 amperes. 
♦  Includes and (1) Load Shunt (total distribution load) 
♦  See 
Restrictions 
The maximum number of Distribution Cabinets in a system is three (3).  Each Distribution Cabinet must be 
mounted immediately above a Power Shelf with zero (0) inches of rack space between units to accommodate 
the furnished busbar links.  Adequate vertical mounting space must be provided above each Distribution 
Cabinet to accommodate distribution and battery cabling.   
Fuses and/or circuit breakers are to be mounted from right to left, starting with the highest capacity and 
working to the lowest capacity. 
Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG. 
Ordering Notes 
1)  Order circuit breakers, as required, per Table 
2)  Order fuses, as required, per Tables 
3)  Order one (1) Part No. 117201 fuseholder per fuse ordered in 2) above. 
4)  Order one (1) Part No. 524690 mounting kit per circuit breaker or fuseholder ordered in 1) or 3) above.  
Kit includes bullet socket busbar and hardware for mounting load and return lugs for one distribution 
position. 
5)  Order one (1) Load lug (one-hole, 1/4” bolt clearance hole) and one (1) Load Return lug (two-hole, 1/4” 
bolt clearance holes on 5/8” centers) as required for each distribution position per Tabl