System Application Guide 
Issue AE, January 31, 2007 
Spec. No. 582135000 (Model LXP48F1) 
 
Page 18 of 43 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
ACCESSORY INFORMATION 
Distribution Devices 
Bullet Nose Type Circuit Breakers 
Each circuit breaker plugs into a single mounting position. 
Ordering Notes 
1)  Order circuit breakers per Table 
Note:  Load should not exceed 80% of device rating. 
Caution:  A circuit breaker with a rating greater than 75 amperes SHALL HAVE an empty mounting 
position between it and any other overcurrent protective device. 
Caution:  The maximum size circuit breaker used in ambient temperatures above +50°C ambient 
shall be 40 amperes. 
2)  Order one (1) Part No. 524690 mounting kit for each circuit breaker ordered. 
3)  For lug and wire size selection, refer to Table 
BULLET NOSE TYPE CIRCUIT BREAKERS 
AMPERE 
RATING 
PART NUMBER 
Electrical/ 
Mechanical Trip
1
 
(Black Handle) 
PART NUMBER 
Electrical Trip
2
 
(White Handle) 
1 101596 
102272 
3 101597 
102273 
5 101598 
102274 
10 101599 
102275 
15 101600 
102276 
20 101601 
102277 
25 101602 
102278 
30 101603 
102279 
35 101604 
102280 
40 101605 
102281 
45 121997 
121998 
50 101606 
102282 
60 101607 
102283 
70 101608 
102284 
75 101609 
102285 
80 121995 
121996 
100 101610 
102286 
Circuit Breaker Alarm Operation: 
1
 
Provides an alarm during an electrical or manual trip condition. 
Provides an alarm during an electrical trip condition only. 
Unless otherwise specified, breakers are to be mounted from right to left 
starting with the highest capacity and working to the lowest capacity. 
Table 1