TPS/TLS-Type Fuses 
A single fuseholder provides for installation of a 3 to 100 ampere Bussmann TPS-type or Littelfuse TLS-type 
fuse.  This fuseholder plugs into a single mounting position on the compatible distribution bus options 
described in this document.  This fuseholder provides a GMT-A alarm type fuse, which operates open to 
provide an alarm indication if the distribution fuse opens. 
Ordering Notes 
1)  Order fuses per Table 
Note:  Load should not exceed 80% of device rating. 
Caution:  A fuse with a rating greater than 75 amperes SHALL HAVE an empty mounting position 
between it and any other overcurrent protective device. 
Caution:  The maximum size fuse used in ambient temperatures above +50°C ambient shall be 40 
amperes. 
2)  Order one (1) Part No. 117201 TPS/TLS-type fuseholder for each fuse. 
3)  Order one (1) Part No. 524690 mounting kit for each fuseholder ordered. 
4)  For lug and wire size selection, refer to Table 
 
TPS/TLS-TYPE FUSES 
AMPERE RATING 
PART NUMBER 
3 248230900 
5 248231000 
6 248231200 
10 248231500 
15 248231800 
20 248232100 
25 248232400 
30 248232700 
40 248233300 
50 248233900 
60 248234200 
70 248234500 
80 118413 
90 118414 
100 118415 
TPS/TLS-Type Fuseholder* 
117201 
*  Fuseholders are not furnished and must be ordered as required.  
Order (1) Part No. 117201 for each fuse position required.  
Fuseholder includes (1) alarm fuse (Bussmann GMT-A 18/100 amp; 
Emerson Network Power 248610301) and (1) alarm fuse safety cover 
(Emerson Network Power P/N 248898700).   
 
Unless otherwise specified, fuses are to be mounted from right to left 
starting with the highest capacity and working to the lowest capacity. 
Table 2