Emerson 710NPBA Manuel D’Utilisation

Page de 60
User Instructions 
UM581127000 
Spec. No. 581127000 (Model 710
NPBA
Issue AB, March 22, 2012 
 
 
Chapter 4. Troubleshooting and Repair 
Page 17 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
2)  If a password screen opens, a password must be entered to allow the User to 
make adjustments.  If a password was previously entered and has not yet timed 
out, skip this step and proceed to step 3).  Otherwise, to enter a password, with 
the cursor at the User Name field 
(default is “Admin”), press the down arrow key 
to move cursor down to the password line.  Press ENT
.  “0” is highlighted.  Press 
the up arrow key once to change the “0” to”1” (default password is “1”), then 
press ENT twice.  (Note:  If you have been assigned a unique User Name and 
password, follow this procedure to enter these.)
 
3)  With the Manual menu screen displayed, navigate to and select 
Converter” 
(ENT) / 
All Conv Ctrl” (ENT). 
4)  Navigate to 
Clear Comm Fail”.  Press ENT.  “Yes” highlights. 
5)  Press ENT to select the operation.  Press ENT again to confirm. 
6)  Return to the Main screen by repeatedly pressing ESC (escape). 
Clearing a Rectifier Lost Alarm 
If the ACU+ Controller resets while a rectifier communications fail alarm is active, the 
rectifier communications fail alarm is replace with a rectifier lost alarm.  To clear the 
alarm, perform the following procedure. 
Procedure 
1)  With the Main screen displayed, press ENT to go to the Main Menu.  Navigate to 
and select 
Manual” (ENT). 
2)  If a password screen opens, a password must be entered to allow the User to 
make adjustments.  If a password was previously entered and has not yet timed 
out, skip this step and proceed to step 3).  Otherwise, to enter a password, with 
the cursor at the User Name field 
(default is “Admin”), press the down arrow key 
to move cursor down to the password line.  Press ENT
.  “0” is highlighted.  Press 
the up arrow key once to change the “0” to”1” (default password is “1”), then 
press ENT twice.  (Note:  If you have been assigned a unique User Name and 
password, follow this procedure to enter these.)
 
3)  With the Manual menu screen displayed, navigate to and select 
Rectifier” (ENT) 
All Rect Ctrl” (ENT). 
4)  Navigate to 
Clear Rect Lost”.  Press ENT.  “Clear” highlights. 
5)  Press ENT to select the operation.  Press ENT again to confirm. 
6)  Return to the Main screen by repeatedly pressing ESC (escape). 
Clearing a Converter Lost Alarm 
If the ACU+ Controller resets while a converter communications fail alarm is active, the 
converter communications fail alarm is replace with a converter lost alarm.  To clear the 
alarm, perform the following procedure. 
Procedure 
1)  With the Main screen displayed, press ENT to go to the Main Menu.  Navigate to 
and select 
Manual” (ENT). 
2)  If a password screen opens, a password must be entered to allow the User to 
make adjustments.  If a password was previously entered and has not yet timed 
out, skip this step and proceed to step 3).  Otherwise, to enter a password, with 
the cursor at the User Name field 
(default is “Admin”), press the down arrow key 
to move cursor down to the password line.  Press ENT
.  “0” is highlighted.  Press 
the up arrow key once to change the “0” to”1” (default password is “1”), then