Chapter 4. Troubleshooting and Repair 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
press ENT twice.  (Note:  If you have been assigned a unique User Name and 
password, follow this procedure to enter these.)
 
3)  With the Manual menu screen displayed, navigate to and select 
Converter” 
(ENT) / 
All Conv Ctrl” (ENT). 
4)  Navigate to 
Clear Conv Lost”.  Press ENT.  “Clear” highlights. 
5)  Press ENT to select the operation.  Press ENT again to confirm. 
6)  Return to the Main screen by repeatedly pressing ESC (escape). 
 
 
 
 
REPLACEMENT INFORMATION 
When a trouble symptom is localized to a faulty rectifier module, converter module, 
controller, or system circuit card; that particular device or circuit card should be replaced 
in its entirety.  Other than a rectifier module or converter module fan replacement, no 
attempt should be made to troubleshoot or repair individual components on any rectifier 
module, converter module, controller, or circuit card. 
Refer to SAG581127000 (System Application Guide) for replacement part numbers. 
 
 
 
 
REPLACEMENT PROCEDURES 
Danger: 
Adhere to the “Important Safety Instructions” presented at the front of this 
document. 
Replacing a Rectifier or Converter Module 
Refer to the Rectifier User Instructions (UM1R243000) or Converter User Instructions 
(UM1C24481500) for a rectifier and converter module replacement procedure.  Refer 
also tSystem Troubleshooting Information in this chapter. 
The rectifier or converter module being replaced is assigned by the ACU+ the lowest 
available identification number.  If desired, you can change the identification number, see 
“Configuring the ACU+ Identification of Rectifier Modules” or “Configuring the ACU+ 
Identification of Converter 
Modules” in Chapter 5 of the separate Power System 
Installation Manual (IM581127000). 
Replacing the ACU+ Controller 
Refer to the ACU+ User Instructions (UM1M820BNA) for a controller replacement 
procedure.