Chapter 4. Troubleshooting and Repair 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
Replacing a Bullet Nose Circuit Breaker 
Procedure 
Note:  Refer to Figure 4-3 as this procedure is performed. 
1)  Open the distribution cabinet
’s front door by turning the latch in the 
counterclockwise position. 
2)  Operate the defective circuit breaker to the OFF position. 
3)  Gently rock the defective circuit breaker up and down while pulling firmly outward 
until the breaker is free from the distribution panel. 
4)  Ensure that the circuit breaker is in the OFF position, and is of the correct rating. 
5)  Orient the circuit breaker as shown in Figure 4-3.  Insert the terminals on the rear 
of the circuit breaker into their corresponding sockets on the distribution panel.  
Ensure the alarm contact on the back of the circuit breaker makes contact with 
the alarm terminal on the mounting circuit card.  Push distribution device in firmly 
until fully seated in the distribution panel. 
6)  Operate the replacement circuit breaker to the ON position. 
7)  Verify no Circuit Breaker Alarms are active. 
8)  Close the distribution cabinet
’s front door.  Turn the latch clockwise to secure the 
door. 
 
Figure 4-3 
Replacing a Bullet Nose Circuit Breaker 
Insert these terminals
into corresponding sockets
on distribution panel.
Longer Side
to the Bottom
Shorter Side
to the Top
Lettering on
handle must be
right side up.
Turn off
before installing.