Emerson 710NPBA Manuel D’Utilisation

Page de 60
UM581127000 
User Instructions 
Issue AB, March 22, 2012 
Spec. No. 581127000 (Model 710
NPBA
 
Page 24 
Chapter 4. Troubleshooting and Repair 
 
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy 
Systems, North America, Inc.  Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited. 
Replacing a TPL-B Fuse 
Procedure 
Note:  Refer to Figure 4-4 as this procedure is performed. 
1)  Open the distribution cabinet
’s front door by turning the latch in the 
counterclockwise position. 
2)  Remove the fuse case from the mounted fuse block by grasping its handle and 
pulling it straight out. 
3)  Open the fuse case. 
4)  Remove the open fuse from the fuse case and replace it with the same type and 
rating. 
5)  Close the fuse case. 
6)  Push the fuse case securely back into the mounted fuse block. 
7)  Replace the alarm fuse located in the front of the TPL-B fuse block.  Replace 
only with a fuse of the same type and rating.  Ensure that a plastic safety cover is 
installed on the alarm fuse. 
8)  Close the distribution cabinet
’s front door.  Turn the latch clockwise to secure the 
door. 
 
 
Figure 4-5 
Replacing a TPL-B Fuse 
Fuse Case
Open Fuse Case View
TPL Fuse
Fuse Installed in
Open Fuse Case
(rear view)
Fuse Installed in
Closed Fuse Case
(rear view)
Fuseblock
(P/N 516241)
GMT-18/100A Alarm Fuse
(P/N 248610301) and
GMT-X Safety Fuse Cover
(P/N 248898700)
(Both are provided
w/ fuseblock)