Emerson 160 Manuel D’Utilisation

Page de 79
Chapter 3  Electrical Installation      23 
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA    User Manual 
2. Intellislot intelligent communication ports 
There are three intelligent communication ports (Intellislot 1, Intellislot 2, and Intellislot 3) available for installing 
optional SNMP card, UPS JBUS/MODBUS adapter, and relay card. 
The serial ports RS232-1, RS232-2, and the Intellislot intelligent communication ports share the same communication 
resources, as described in Table 3-7. 
Table 3-7    Communication port resource deployment table 
Port 
On the UPS   
LCD screen, under 
Settings, controlled by: 
Monitoring devices supported
 
Baud 
rate 
 
Comments 
 
SNMP card 
9600 
JBUS/MODBUS adapter 
Any 
Intellislot 2
 
Comm 1 
Relay card 
Any 
Not simultaneous with 
RS232-2 
SNMP card 
9600 
JBUS/MODBUS adapter 
Any 
Intellislot 1
 
Comm 2 
Relay card 
Any 
Not simultaneous with 
RS232-2 
SNMP card 
9600 
JBUS/MODBUS adapter 
Any 
Intellislot 3
 
Comm 3 
Relay card 
Any 
Not simultaneous with 
RS232-2 
RS232-1 
Comm 1 
UPSitePlusTM UPS monitoring software 
9600 
RS232-2 Comm 
Commissioning and service software (only for use by 
authorized commissioning and service personnel) 
9600 
Not simultaneous with the 
three Intellislot ports 
 
3.3.2   Battery Control 
The BCB is controlled by the BCB control board. Both are located within the BCB box. This board controls the circuit 
breaker's undervolts release coil and also provides a path for the circuit breaker auxiliary contacts to signal the circuit 
breaker status back to the UPS control logic.   
All connections between the BCB control board and the UPS module are made through the auxiliary terminal block 
X3 located on the base of the UPS Cabinet. X3 is shown in Figure 3-8 and described in Table 3-8. 
 
FB
GND
OL
+12V
TMP_T
GND
LM355+
LM355+ GND
DRV
DRV_GND
BCB status feedback
BCB connection detection
Battery temperature sensing 1
Battery temperature sensing 2
BCB drive
Not connected
NC
NC
X3
1
2
3
4
5
6
7
8
9
10
11
12
 
Figure 3-8    Auxiliary terminal block X3