38      Chapter 4  Operator Control And Display Panel 
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA    User Manual 
Alarm message 
Description 
Byp. feedback fault 
UPS feeds output voltage back to the mains grill through bypass due to shortcircuit of static switch 
on bypass side during mains failure. In this case, lack of protective bypass switch or improper 
connection of switch auxiliary contact will endanger the user safety. Special attention should be paid 
to this 
INV drive circuit fault 
Improper connection of inverter drive cable, or equipment type setting error 
Bypass disconnect 
closed 
Bypass switch closed 
Bypass disconnect open 
Bypass switch open 
Maint. disconnect closed 
Maintenance bypass switch closed   
Maint. disconnect open 
Maintenance bypass switch open 
Output disconnect closed 
Output switch closed 
Output disconnect open 
Output switch open 
Check UPS output 
The UPS is off and has no output 
Output disabled 
If the UPS auto-recovery after EOD function is disabled, after UPS shutdown due to battery 
discharge to EOD (end-of-discharge) voltage, when the mains power is restored, the UPS will not 
restart automatically, and the LCD will display this alarm message 
Normal mode 
The UPS is in Normal mode 
Battery mode 
The UPS is in Battery mode 
Source share mode 
The UPS is in Source Share mode 
Bypass mode 
The UPS is in Bypass mode