Emerson 240V Manuel D’Utilisation

Page de 44
Installation
11
2.3
Cable Installation
2.3.1 Wiring Preparation
Removing the Cover Plates
On the back 
of the UPS, 
cover plates 
are over the 
input and 
output 
terminals, as 
shown at 
right. Keep 
screws and 
plates to one 
side.
Configuring the Bypass Voltage (TB2)
The UPS voltage is factory-set to 208 V. 
Should the user have a utility supply of 240 V, 
the bypass voltage jumper will have to be 
changed to ensure correct output voltage. 
After selection, retorque jumper screws to 
28 in-lb.
Customer-Provided Overcurrent Protection
A branch rated overcurrent protection device (cir-
cuit breaker or fused disconnect switch) must be 
installed for the AC input.
If the start-up is on bypass, the UPS has a six-
cycle inrush current that is up to 20 times the 
rated output current. This must be taken into 
account when selecting the overload protection 
device at the AC input supply distribution point. 
To avoid random tripping on start-up, it is recom-
mended that the AC input supply be protected 
with a circuit breaker capable of withstanding 
this initial inrush.
This UPS is fitted with EMI suppression filters. 
Earth leakage current is less than 40mA. Tran-
sient and steady state earth leakage currents may 
occur when starting the equipment. This should 
be taken into account when selecting ground cur-
rent detection devices, as the earth leakage cur-
rents of both the UPS and load will be carried.
Input and output cables must be run in separate 
conduits.
!
WARNING
Please read this section thoroughly 
before attempting to install wiring to 
this unit.
This UPS should be installed by a 
qualified / certified electrician.
Remove Cover Plates
208 V
(default)
240 V
OR
Bypass Voltage Jumper