Troubleshooting
31
4.0
T
ROUBLESHOOTING
4.1
Active Alarms
In the event of an alarm, the User Interface LCD will display the last message regardless of the 
default screen. A list of possible alarm messages is displayed below. If you encounter one of these or 
other alarm messages and are unsure of the corrective action to take, please contact a qualified Lie-
bert representative at the number listed on the back of this manual.
User Interface Text
Cause
Action
Main Control Failure The Nfinity system has detected a 
System Control Module failure.
Identify and replace the failed System Control Module or 
contact Liebert Global Services for support.
Power Module Fail
The Nfinity system has detected a Power 
Module failure.
Identify and replace the failed Power Module or contact 
Liebert Global Services for support.
Battery Module Fail
The Nfinity system has detected a Battery 
Module failure.
Identify and replace the failed Battery Module or contact 
Liebert Global Services for support.
Redun. Control Fail
The Nfinity system has detected a 
System Control Module failure.
Identify and replace the failed System Control Module or 
contact Liebert Global Services for support.
Battery Card Failure The Nfinity system has detected an 
Intellislot Battery Card failure.
Identify and replace the failed Intellislot Battery Card or 
contact Liebert Global Services for support.
UPS On Battery
The Nfinity is drawing power from the 
batteries, not from utility.
Verify input breaker is closed. Verify input voltage is 
present and correct voltage. Verify input frequency is 
correct.
Reminder alarm - 
Check air filter
The fan filter reminder time has elapsed.
Check and clean the fan filter and acknowledge the alarm. 
This alarm may be disabled or the interval between these 
alarms can be configured via the User Interface.
Short Circuit 
Recovery - Please 
Wait
User tried to turn the output on following a 
short circuit on the output without waiting 
for the required 30 seconds to expire.
Wait for at least 30 seconds and then turn the output on.
Power Module N+1 
Redundancy Alarm
Number of power modules is not 
adequate to provide power redundancy.
Reduce the UPS’s load, add power modules to the frame 
or disable the alarm feature via the User Interface.
Output Off - Output 
Short Circuit
A short circuit was detected on the output. Correct short (or extreme overload condition) and turn on 
the UPS’s output.
UPS Output 
Overload
The load on the Nfinity exceeded the 
capacity of the active power modules.
Reduce the UPS’s load or add power modules.
Output exceeds
max load setting
This will occur if the max load alarm is 
enabled, and the measured load at the 
UPS’s output is greater than the value 
set.
Reduce the UPS’s load, increase the Maximum Load 
Alarm limit via configuration or disable the Maximum Load 
Alarm limit via configuration.
Output Off- 
Overload, bypass 
unavailable
Normally a severe overload will cause the 
unit to go to automatic bypass. This event 
informs the user that bypass was not 
qualified so the unit dropped the load to 
protect itself.
Reduce the UPS’s output load and verify that the UPS’s 
bypass source is qualified (amplitude and frequency). 
Verify that the configuration voltage and frequency 
settings are properly selected.
Switch To 
Manual Bypass
The Nfinity is on automatic bypass. 
Manual bypass switch should be 
activated before servicing.
Transfer Nfinity to manual bypass and call Liebert service 
for assistance.
Load Exceeds 
Battery Module 
Capacity
The measured load on the output will 
cause the battery modules to exceed their 
limits if the UPS transfers to battery 
mode.
Reduce the UPS’s load or add battery capacity. If external 
non-modular battery cabinet(s) are added, verify that the 
UPS’s configuration is set to match the external battery 
amp-hour rating and charger rating.
Bypass source 
not qualified
The input voltage is not within the 
specified voltage or frequency range so 
the UPS will not allow an automatic or 
manual transfer to bypass.
Verify UPS’s configuration for voltage and frequency. 
Check UPS’s input breaker; disable this alarm if desired 
via configuration.
Load exceeds 
frame limit
Load is greater then the rated frame limit. Reduce the UPS’s load.