Emerson 240V Manuel D’Utilisation

Page de 44
Troubleshooting
32
Assert manual 
bypass
A user-initiated transfer to bypass will 
assert this alarm, instructing the user to 
enable the manual bypass switch. Once 
the manual bypass is asserted, the alarm 
will clear. This is a non-mutable alarm.
Engage the manual bypass switch (located at the bottom 
front on the left hand corner of the unit). Once engaged, 
the switch may be de-asserted to return to normal 
operation.
Remote shutdown 
on COM port 1 
active
The most likely cause is that the incorrect 
cable has been connected to the COM 
port between the UPS and the host.
Check for a wiring problem to the Shutdown On Battery at 
the COM1 connector. If this problem is not addressed, the 
unit will shut down shortly after switching to battery 
operation.
Battery Test 
Weak Battery
The battery was determined to be weak 
as a result of the battery test.
Depending on the age of the batteries, it may be 
appropriate to replace all batteries in the system. 
Schedule a battery test so that the system operation is 
double-checked once the batteries become fully charged.
Battery Test 
Failure
One or more of the following was 
detected during a battery test: 
• UPS output regulation failure was 
detected.
• A battery module warning or failure 
occurred.
• A system control failure occurred.
Replace the battery modules that have active failures/
warnings. Depending on the age of the batteries, it may be 
appropriate to replace all batteries in the system. 
Schedule a battery test so that the system operation is 
double-checked once the batteries become fully charged.
Battery Cabinet 
Not Connected
This is intended to detect a situation 
where a Modular battery cabinet has 
been connected for communication, but 
the power busses are not connected.
Check that the Modular Battery breaker is closed. Verify 
proper connections between UPS and Modular Battery 
Cabinet.
Don’t Remove SC
The only good System Control Module 
lock lever was raised with the output on 
and the unit is not on bypass.
• Lower the lock lever on the System Control Module.
• Provide qualified bypass power so that transfer to 
bypass is possible.
• Add a redundant System Control Module so that the load 
is not dropped.
Failure: Select 
Manual Bypass
The System Controller detected a failure. 
Select manual bypass so that the unit can 
be serviced.
Transfer UPS to manual bypass and contact Liebert 
Global Services.
Output Off - 
bypass unavailable
This event informs the user that bypass 
was not qualified so the unit dropped the 
load to protect itself.
Verify that the UPS’s bypass source is qualified (amplitude 
and frequency). Verify that the configuration voltage and 
frequency settings are properly selected.
Last UPS Shutdown 
By Emergency 
Power Off
REPO switch was pressed.
If REPO wasn’t pressed, check for REPO wiring problems.
External Battery 
Module Warning
The energy delivered from the Non-
Modular battery did not meet 
programmed battery capacity.
Verify proper connections between UPS and Non-Modular 
Battery Cabinet. Reenter the amp-hour rating for the 
external battery (set the amp-hour entry to zero and press 
the return key, then reset it to the appropriate value for the 
external battery). If the problem persists, the external 
battery should be replaced.
Battery Module 
Not Ready
A battery module is not ready. In most 
cases, one or more battery modules 
should indicate a warning/failure 
condition.
Ensure that the battery module is fully seated and the 1/4 
turn fastener is engaged. If the problem persists, replace 
the battery module with warning/failure condition indicated 
at the User Interface. If no User Interface warning/failure 
of battery module, look for the battery module with LEDs 
indicating a problem and replace that unit.
Power Module 
Not Ready
A power module is not ready. In most 
cases, one or more power modules 
should indicate a warning or failure 
condition.
Ensure that the power module is fully seated and the 1/4 
turn fastener is engaged. If the problem persists, replace 
the power module with warning/failure condition indicated 
at the User Interface. If no User Interface warning/failure 
of power module, look for the power module with LEDs 
indicating a problem and replace that unit.
User Interface Text
Cause
Action