The relay card provides voltage-free contact closures for remote monitoring of alarm conditions.
Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS 
signals, the easy-to-install card integrates with AS/400 computers (additional cable required) and 
other relay contact monitoring systems.
The relay card is rated for 24 VAC/DC at 1A and supported in any of the three Liebert
®
 IntelliSlot
®
 
bays on the Liebert NX
.Refer to the Liebert Intellislot Relay Card user manual, SL-23211, for pin 
and jumper configuration. The manual is available at Liebert’s Web site: