Options
109
MultiPort 4 Card
The MultiPort 4 card provides four sets of voltage-free contact closures for remote monitoring of 
alarm conditions UPS operation On Battery and Low Battery condition. A typical application is to 
allow a maximum of four computer systems to simultaneously monitor the status (e.g., utility power 
failure-low battery) of a single UPS.
This card is supported in any of the three Liebert
®
 IntelliSlot
®
 bays on the Liebert NX
.
Figure 70 MultiPort 4 card pin assignment
12.2 LBS Mode—Load Bus Synchronization
The function of LBS is to keep the output of two independent UPS systems (single unit or multiple 
unit) in synchronization even when the two systems are operating in different modes (bypass/
inverter) or on batteries. It is usually used with a Static Transfer Switch connected to the critical load 
to achieve dual bus configuration.
12.2.1 Remote Alarm Monitor
Status and alarm conditions are available on an optional remote alarm monitor (RAM) panel, which is 
driven by volt-free alarm status contacts (from an optional relay alarm board).
12.3 Replacing Dust Filters
1. Open the UPS door.
2. The dust filters are behind the door. For each filter, there is a bracket on either side holding the 
dust filter in place, as shown in Figure 71.
3. Remove one bracket and loosen the other. The second bracket need not be removed.
4. Remove the old filter and replace with the new filter.
5. Reinstall the bracket that was removed and tighten the other bracket.
Figure 71 Dust filter replacement
NOTE
In LBS configuration, both units must be supplied from the same utility source.
UPS
CPU
CPU
CPU
CPU
Pin
Assignment
Description
1
Low Battery
2
Not  Used
3
Not  Used
4
Not  Used
5
Not  Used
6
Not  Used
7
Low Battery Common
8
Utility Fail Common
9
Utility Fail
 
Bracket
Sems screw
Bracket