Emerson 40-200KVA Mode D'Emploi

Page de 132
Liebert
®
 BDC
42
7.1.1 Bypass Mode
When the Liebert BDC is in Bypass mode, it provides an alternate path for power to the connected 
equipment. Should the UPS need to be taken out of service for limited maintenance or repair, manual 
activation of the bypass will cause an immediate transfer of the equipment from the UPS inverter to 
the bypass source. In this mode, power will still be supplied to the UPS; however, the load is NOT 
protected by the UPS. 
7.2
Maintenance Mode
When the Liebert BDC is in Maintenance mode (MBB closed; BIB/MIB open), it provides an alternate 
path for power to the connected equipment should the UPS need to be taken out of service for limited 
maintenance or repair. In this mode of operation, no power is supplied to the UPS and the load is 
NOT protected by the UPS.
7.3
Locating the Cabinet
This Liebert BDC may be mounted to the left of the UPS or installed as a stand-alone unit. In either 
case, ensure that the unit is in a well-ventilated area and that there is clearance for access to the 
switches and cable connections as required by national and local codes.
7.4
Cable Installation
7.4.1 Wiring Preparation
Be sure that the unit is not connected to any AC utility power source or UPS before installing any 
wiring to this unit. This Liebert BDC should be installed by a qualified / certified electrician.
Removing the Cover Plates
Plates cover the input and output terminals on the front of the Liebert BDC. Remove these and keep 
the screws and plates for reinstallation.
7.4.2 Power Cable Installation
Refer to Table 15 when selecting cables.
WARNING
Risk of electrical shock and arc flash. Can cause property damage, injury and death.
Read this section thoroughly before attempting to install wiring to this unit. Read and 
comply with all warnings and cautions in this manual.
Table 15
Power cable size selection (Copper Wire Only)
Bus Type
Terminal
Main Input
Bypass Input
Output
Single Input
Dual Input
Dual Input
Liebert
®
 NX
 40kVA UPS
4
4
4
3
Liebert NX 60kVA UPS
1
1
2
2
Liebert NX 80kVA UPS
2/0
2/0
1/0
1/0
Liebert
®
 NX
 100kVA UPS
4/0
4/0
2/0
2/0
Liebert NX 120kVA UPS
250
250
4/0
4/0
Liebert NX 160kVA UPS
2-3/0
2-3/0
2-3/0
2-3/0
Liebert NX 200kVA UPS
2-4/0
2-4/0
2-4/0
2-4/0
Liebert NX 480V
Battery Cabinet DC Input Bus
225A
350A
600A
4/0AWG
400kcmi
2-350kcmil
NOTE
Transient and steady state earth leakage currents may occur when starting the equipment. 
This should be taken into account when selecting ground current detection devices because 
these will carry the earth leakage currents of both the UPS equipment and the load.