Emerson 40-200KVA Mode D'Emploi

Page de 132
Installation Drawings
54
Figure 28 Liebert
®
 NX
 160-200kVA dimensions—front and left side
Table 26
Electrical specifications, Liebert NX 160-200kVA
Rating, kVA
Voltage
Heat 
Rejection
BTU/hr
Cooling Air
CFM
Input
Output
160
480
480
35,900
1590
200
480
480
47,000
1590
Source: U3819621, Rev. 1
NOTES:
1. All dimensions are in inches [mm]. Weight est. 2201 lb. (1000kg).
2. 24" [610] minimum clearance above unit required for air exhaust, and 36" [914] minimum service clearance at front of unit.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace.
5. Control wiring and power wiring must be run in separate conduits.
6. Aluminum and copper-clad aluminum cables are not recommended.
7. All wiring is to be in accordance with national and local electrical codes.
8. Depth dimensions include front door and rear panel.
9. Width dimension includes side panels. Subtract 2.2" (56mm) when removing both side panels.
U3819621
Rev. 1
.8 (19)
Front
Frame
.9 (23)
Outside
Frame
.4 (10)
Outside
Frame
1.6 (41) Outside
Frame Typ
1.6 (41) Outside
Frame Typ
4.1 (104)
3
(76)
2.7 (68)
Front
Frame
TOP VIEW (Door Open)
LEVELER SPACING
Looking Top Down
BOTTOM
(Looking Top Down)
Low Voltage
 Entry
5.1 x 3.9
(130x100)
61.9
(1573)
33.1
(842)
Typ
38.9 (987)
To Centers of Caster Brkt. Typ
27.1 (688)
To Centers
of Caster
Brkt. Typ
5.7 (146) Typ
5.0 (127) Typ
FRONT
43.7 (1111) Typ.
48.9 (1242)
39.0 (990) to Display
38.5 (978)
RIGHT SIDE
See Detail A
REAR
7.3 (186)
Outside Frame
1.9 (49)
Front Frame
Front
32.3 x 6.4 (820x163)
Cable Entry Panel
78.7
(2000)
Power Cable
Entry
14 x 13 (355x330)
DETAIL A