Specifications and Technical Data
93
11.3 Cable size and tightening torques
Table 28
External cabinet dimensions, including side panels
Wide Parallel Cabinet
 
Unit
 
Width
 
Depth
 
Height
 
mm (inch)
1240 (48.8)
965 (38)
2000 (78.7)
Narrow Parallel Cabinet
 
Unit
 
Width
 
Depth
 
Height
 
mm (inch)
845 (33.2)
965 (38)
2000 (78.7)
33 in. Battery Cabinet
 
Unit
 
Width
 
Depth
 
Height
 
mm (inch)
845 (33.2)
965 (38)
2000 (78.7)
Table 29
Cable size tightening torque at Liebert NX 40kVA UPS terminals
Bus Type
Cable Size
(Copper Wire Only)
Torque to Tighten
Terminal Bus & Lug Body
Main Input
(Single Input)
4
10  N-m
Main Input
(Dual Input)
4
10  N-m
Bypass Input
(Dual Input)
4
10  N-m
Output
3
10 N-m
Table 30
Cable size tightening torque at Liebert NX 60kVA UPS terminals
Bus Type
Cable Size
(Copper Wire Only)
Torque to Tighten
Terminal Bus & Lug Body
Main Input
(Single Input)
1
10  N-m
Main Input
(Dual Input)
1
10  N-m
Bypass Input
(Dual Input)
2
10  N-m
Output
2
10 N-m
Table 31
Cable size tightening torque at Liebert NX 80kVA UPS terminals
Bus Type
Cable Size
(Copper Wire Only)
Torque to Tighten
Terminal Bus & Lug Body
Main Input
(Single Input)
2/0
10 N-m
Main Input
(Dual Input)
2/0
10 N-m
Bypass Input
(Dual Input)
1/0
10 N-m
Output
1/0
10 N-m