11.1 Lug Size and Torque Requirements
Use commercially available solderless lugs for the wire size required for your application. Refer to 
Table 24Connect wire to the lug using tools and procedures specified by the lug manufacturer.
Table 24
Torque specifications
Nut and Bolt CombinationS
Bolt Shaft Size
Grade 2 Standard
Electrical Connections
with Belleville Washers
Lb-in
N-m
Lb-in
N-m
1/4
53
6.0
46
5.2
5/16
107
12
60
6.8
3/8
192
22
95
11
1/2
428
22
256
29
Circuit Breakers With Compression Lugs (For Power Wiring)
Wire Size or Range
Lb-in
N-m
#6 - #4
100
11
#3 - #1
125
14
1/0 - 2/0
150
17
3/0 - 200 MCM
200
23
250 - 400 MCM
250
28
500 - 700 MCM
300 
34
Circuit Breakers With Compression Lugs (For Power Wiring)
Current Rating
Lb-in
N-m
400 - 1200 Amps
300.00
34.00
Terminal Block Compression Lugs (For Control Wiring)
AWG Wire Size or Range
Lb-in
N-m
#22 -#14
3.5 to 5.3
0.4 to 0.6
NOTE: Use the values in this table unless the equipment is labeled with a different torque value.
Table 25
Battery torque rating
 
Battery
 
Initial Torque
in-lb (N-m)
 
UPS12-100MR
 
40 (4.5)
 
UPS12-150MR
 
25 (2.8)
 
UPS12-210MR
 
25 (2.8)
 
UPS12-300MR
 
110 (12.4)
 
UPS12-350MR
 
110 (12.4)
 
UPS12-400MR
 
110 (12.4)
UPS12-490MRLP
 110 (12.4)
UPS12-540MR
110 (12.4)
HX300
60 (6.8)
HX330
60 (6.8)
HX400
60 (6.8)
HX500
60 (6.8)
HX540
60 (6.8)