Emerson 480V Manuel D’Utilisation

Page de 112
UPS Specifications
33
5.0
UPS S
PECIFICATIONS
These specifications describe requirements for the Liebert NX UPS.
5.1
Conformity and Standards
The UPS has been designed to conform to the following standards:
• IEC 61000-4-5
• ASME
• CSA 22.2, No. 107.1
• FCC Part 15, Class A
• ISO 9001
• National Electrical Code (NFPA-70)
• NEMA PE-1
• OSHA
• UL Standard 1778
The UPS system has UL and c-UL approval. 
5.2
UPS Environmental 
The UPS is designed to operate under the following environmental conditions without damage or deg-
radation in electrical operating characteristics:
5.3
UPS Mechanical Characteristics
Table 6
Environmental characteristics
Rated Power
40kVA
60/80kVA
100/120kVA
160/200kVA
Operating Temperature, UPS
32°F to 104°F (0°C to 40°C)
Optimal Operating Temperature, Battery
68°F to 86°F (20°C to 30°C)
Relative Humidity
0 to 95%, non-condensing
Acoustical Noise, dBA at 39 in. (1m)
(Fans at Low Speed)
61
61
63
68.5
Altitude of Operation
≤1000m per IEC 62040/3
Storage-Transport Temperature, UPS, 
-4°F to 158°F (-20°C to 70°C)
Storage-Transport Temperature, Battery
-4°F to 86°F (-20°C to 30°C)
Table 7
UPS mechanical characteristics
Parameter
40/60/80kVA
100/120kVA
160/200kVA
Width, in. (mm)
23.6 (600)
48.8 (1239)
Depth, in. (mm)
38 (965)
38.5 (979)
Height, in. (mm)
78.5 (2000)
78.5 (2000)
Heat Dissipation, BTU/H (kWH)
20,273 (5.9)
28,196 (8.3)
46,400 (13.6)
Airflow, CFM (m
3
/h)
1760 (2990)
1668 (2834)
Cable Entry
Bottom or Top
Color
Black (Z-0350)
Protection Grade (with open/closed front doors)
IP 20
Weight, lb (kg)
1180 (535)
1290 (585)
2201 (1000)