Emerson 480V Manuel D’Utilisation

Page de 112
UPS Specifications
35
5.4.1 Input Rectifier
Battery
Unit
Rating
Nominal
Discharge
Current
Maximum
Discharge
Current
OCP
Device
Rating
Bolt
Size
Maximum 
Recommended 
Lug
(Thomas & 
Betts Part #)
Compression
One-Hole; 3/8" 
bolt
40
82 at 480VDC
103 at 384VDC
125
M8
54106
60
122 at 480VDC
155 at 384VDC
175
M8
54107
80
163 at 480VDC
206 at 384VDC
225
M8
54152-TB
100
204 at 480VDC
258 at 384VDC
300
M8
54157
120
244 at 480VDC
309 at 384VDC
350
M8
54167
160
367 at 480VDC
412 at 384VDC
450
M10
54115
200
408 at 480VDC
515 at 400VDC
600
M10
54115
1. Nominal (Nom) current is based on full rated output load.
2. Maximum (Max) current (125% of nominal) is short duration for battery recharge conditions.
3. UPS input and bypass cables must be run in separate conduit from output cables.
4. Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.
5. OCPD = Overcurrent Protection Device. Recommended AC input and AC output overcurrent protection represents 125% of nominal full 
load current (continuous) per NEC 215.
6. Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground conductors are recommended. References are per 
NEC 1999.
7. Wiring requirements:
a. AC Input: 3-phase, 3-wire, plus ground.
b. AC Output: 3-phase, 3-wire, plus ground.
8. All wiring is to be in accordance with national and local electric codes.
Table 9
Rectifier input power
Rated Power kVA
40
60
80
100
120
160
200
Rated Voltage, VAC
480
Supply
3-phase, 3-wire plus ground
Input Voltage Tolerance, VAC
(without derating)
384-552
Frequency, Hz
57-66
Power Factor
> 0.99 at full load; >0.98 at half load
Harmonic Current
Less than 3% at full rated UPS output load 
See Table 8 for current ratings.
Overload capacity of input current:
100% Imax <I<125% Imax: 60 min
125% Imax <I<150% Imax: 10 min; >150% load, less than 200msec
Table 10
Input voltage window with derating
Input Voltage Window
(L-L Voltage)
Percentage
of Nominal
Inverter Load,
Percentage
Charger Load,
Percentage
 432VAC to 552VAC
90-115
100%
100%
431VAC to 384VAC
80-89
100%
 30%
383VAC to 360VAC
75-79
100%
 0%
359VAC to 288VAC
60-74
 80%
 0%
Table 8
UPS terminal (continued)