UPS Specifications
36
5.4.2 DC Intermediate Circuit
See Table 8 for current ratings.
5.4.3 Inverter Output
See Table 8 for current ratings.
Table 11
Liebert approved replacement batteries
Battery Manufacturer
Models 
Supplied
Enersys Yuasa
HX300
HX330
HX400
HX500
C&D Dynasty
UPS12-100MR
UPS12-150MR
UPS12-210MR
UPS12-300MR
UPS12-350MR
UPS12-400MR
UPS12-540MR
Table 12
DC intermediate circuit
Rated Power kVA
40
60
80
100
120
160
200
Recommended number
of lead-acid batteries
Total 40 battery blocks of 12VDC (240 cells of 2VDC)
will be supported by UPS
Recommended float charge voltage
2.27VDC *
Recommended boost charge voltage
2.4VDC *
Recommended end of discharge voltage
1.67 - 1.75 VDC
Maximum recharge battery current, A *
14.8
22.2
29.6
37.0
44.4
59.2
74
Maximum boost charge duration, min. *
1800
Boost-float threshold current, A *
0.1 C default
Temperature voltage compensation, mV/°C *
From 0 to 5 mV/deg. C/cell. Default value is 3mV/deg. C/cell.*
Ripple voltage superimposed %
≤ 1
* Set by configuration software and based on usage of VLRA batteries.
Table 13
Inverter output
Rated Power kVA
40
60
80
100
120
160
200
Rated voltage, VAC
480
Supply
3-phase, 3-wire plus ground
Frequency, Hz
 60 (50Hz in frequency converter mode)
Rated Power, kW
36
54
72
90
108
144
180
Three-phase transient
overload, min. load
 105% to 110% for 60 minutes
111% to 125% for 10 minutes
126% to 150% for 1 minute
Voltage Regulation %
±1.0% three-phase RMS average for a balanced three-phase load
±2.0% three-phase RMS average for a 100% unbalanced load
Frequency Regulation %
Nominal frequency regulation is ±0.05% in single module mode,
and+/- 0.25% in parallel mode.
Maximum rate of change
of frequency, Hz/sec
For single mode, the slew rate is adjustable from 0.1Hz/s to 3Hz/s