Emerson 48330 Manuel D’Utilisation

Page de 96
44      Chapter 5  Operating SCU 
ACTURA Flex 48330
 
Power System  User Manual 
Serial 
No. 
Alarm 
Description 
Default 
alarm level
Default 
related 
relay 
Related parameter 
configuration  
14 Batt 
Temp 
Low 
Battery temperature is lower than the 
set value of parameter “Temp 
Threshold: Low Temp”   
Observation
None 
Low temperature alarm 
point 
15 
Amb Temp High 
Ambient temperature is higher than 
the set alarm point 
Observation
None  
16 
Amb Temp Low 
Ambient temperature is lower than 
the alarm point   
Observation
None  
17 No 
TempSensor1 
Temperature sensor 1 has been set, 
but no sensor is actually connected 
Critical None 
 
18 No 
TempSensor2 
Temperature sensor 2 has been set, 
but no sensor is actually connected 
Critical None 
 
19 
TempSensor1 
Err 
Temperature sensor 1 detected 
unreasonable temperature   
Critical None 
 
20 TempSensor2 
Err 
Temperature sensor 2 detected 
unreasonable temperature 
Critical None 
 
21 LLVD 
1. Load disconnection 
2. Manual load disconnection 
Critical 5 
LLVD 
enabled 
22 BLVD 
1. When battery discharges till its 
voltage is lower than the “BLVD 
Volt”, or the discharge time is longer 
than the “BLVD Time”, the BLVD 
contactor will be open automatically 
2. BLVD through manual operation   
Critical 4 
BLVD 
enabled 
23 
Load 1 Faiure 
Over-load, short circuit, manual 
disconnection or alarm circuit faulty 
Critical 6 
 
24 
Load 2 Faiure 
Over-load, short circuit, manual 
disconnection or alarm circuit faulty 
Critical 6 
 
25 
Load 3 Faiure 
Over-load, short circuit, manual 
disconnection or alarm circuit faulty 
Critical 6 
 
26 
Load 4 Faiure 
Over-load, short circuit, manual 
disconnection or alarm circuit faulty 
Critical 6 
 
27 
Load 5 Faiure 
Over-load, short circuit, manual 
disconnection or alarm circuit faulty 
Critical 6 
 
28 
Load 6 Faiure 
Over-load, short circuit, manual 
disconnection or alarm circuit faulty 
Critical 6 
 
29 
Load 7 Faiure 
Over-load, short circuit, manual 
disconnection or alarm circuit faulty 
Critical 6 
 
30 
Load 8 Faiure 
Over-load, short circuit, manual 
disconnection or alarm circuit faulty 
Critical 6 
 
31 
Load 9 Faiure 
Over-load, short circuit, manual 
disconnection or alarm circuit faulty 
Critical 6 
 
32 
Aux Load Fails 
The last route faulty 
Critical 
 
33 Batt1 
Failure 
 
Over-load, short circuit, manual 
disconnection or alarm circuit faulty 
Critical None 
 
34 Batt2 
Failure 
 
Over-load, short circuit, manual 
disconnection or alarm circuit faulty 
Critical None 
 
35 Batt3 
Failure 
 
Over-load, short circuit, manual 
disconnection or alarm circuit faulty 
Critical None