Emerson 48330 Manuel D’Utilisation

Page de 96
46      Chapter 5  Operating SCU 
ACTURA Flex 48330
 
Power System  User Manual 
 
 Note 
When the DC load 9 and its above (load 10, load 11 …) have circuit fault alarm, the 
monitoring module all display “Load 9 Failure” or “Aux Load Fails”. 
 
5.5.4  Changing Audible/Visual Alarm And Alarm Call Back Plan 
There are different audible/visual alarms and call back modes for alarms of different 
levels. For the products in China market, the alarming mode for major alarms and 
critical alarms are the same. 
Table 5-4  Changing audible/visual alarm and alarm call back plan 
Alarm level 
Red 
indicator 
Yellow 
indicator 
Alarm 
horn 
Call back
Remark 
Critical 
ON 
ON 
Callback No. can be set 
Major 
ON 
ON 
Callback No. can be set 
Observation
/ ON 
OFF 
 
No alarm 
OFF 
OFF 
OFF 
 
Therefore, changing the alarm level of different alarms may change their 
audible/visual alarm mode and call back plan too.   
Pressing any key on the monitoring module can silence the alarm sound. The 
sound will disappear and alarm indicator will be off when all alarms are cleared.   
You can configure how long an alarm sound will last, or choose to make no alarm 
sound. For details, see 5.7.11  Alarms Settings. 
5.5.5    Changing Alarm Types Of Dry Contacts 
As one of the alarm type parameter, “Related Relay” refers to the serial No. of the 
dry contract corresponding to the alarm type, whose value is either 1 ~ 8 or “None”. 
“None” means there is no corresponding dry contact. For details, see 4.7.11 Alarms 
Settings
5.5.6    Setting Alarm Type For Dry Contacts 
The Programmable Logic Control (PLC) is configured through the host software.   
The way to configure the PLC function is:   
C = A (Status) * B (Status) 
C: The dry contract serial No. of the corresponding output. Range: 1 ~ 8. 
A, B: The input alarm type. Status: Whether the alarm has been raised.