Emerson 48330 Manuel D’Utilisation

Page de 96
48      Chapter 5  Operating SCU 
ACTURA Flex 48330
 
Power System  User Manual 
Alarm type 
Remark 
BLVD  
Output voltage abnormal 
 
AC power off 
 
Multiple rectifiers alarm 
 
Time for system maintenance (replace the fan)  
Any rectifier comm interrupted 
 
Any rectifier AC power off 
 
Any rectifier over-temperature 
 
Any rctifier faulty 
 
Any rectifier in protection   
 
Any rectifier fan faulty 
 
Any AC derated rectifier 
 
Any temperature derated rectifier   
 
 
For example: To make dry contact No.3 act when battery route 1 is broken but AC 
power is still on, the PLC should be configured like this:   
A: battery route 1, with “status” set as “Alarm”.   
B: AC power off, with “status” set as “No alarm”.   
C: Dry contact No.3 
*: “AND”. 
5.5.7    Set the Alarm Names Through PLC Function   
Connect the serial port of MC to the RS-232 port of SCU, then configure the alarm 
types that correspond to the dry contact outputs through MC. 
An 8 (row) 
% 6 (column) logic matrix is used in configuring these 8 dry contacts. 
Every row in the matrix corresponds to one dry contact. The setting of one dry 
contact has 6 bytes. 
Byte 0: The dry contact is disabled if byte 0 is set to 0, and enabled if byte0 is set to 
1. 
Bytes 1, 3 and 5 are the SN of the 3 alarms respectively. The range of SN is 0-56, 
see section “5.5.3 Alarm List” for details. 
Bytes 2 and 4 define the logic relationship between 3 alarms. The setting of byte 2 
or 4 is 0-3. If the setting is 0, the logic is “AND”; If the setting is “1”, the logic is 
“NOT”; If the setting is “2”, the logic is “OR”; and if the setting is “3”, the logic is 
“AND”.