44 Chapter 5 Operating SCU
ACTURA Flex 48330
Power System User Manual
Serial
No.
Alarm
Description
Default
alarm level
Default
related
relay
Related parameter
configuration
14 Batt
Temp
Low
Battery temperature is lower than the
set value of parameter “Temp
Threshold: Low Temp”
Observation
None
Low temperature alarm
point
15
Amb Temp High
Ambient temperature is higher than
the set alarm point
Observation
None
16
Amb Temp Low
Ambient temperature is lower than
the alarm point
Observation
None
17 No
TempSensor1
Temperature sensor 1 has been set,
but no sensor is actually connected
Critical None
18 No
TempSensor2
Temperature sensor 2 has been set,
but no sensor is actually connected
Critical None
19
TempSensor1
Err
Temperature sensor 1 detected
unreasonable temperature
Critical None
20 TempSensor2
Err
Temperature sensor 2 detected
unreasonable temperature
Critical None
21 LLVD
1. Load disconnection
2. Manual load disconnection
Critical 5
LLVD
enabled
22 BLVD
1. When battery discharges till its
voltage is lower than the “BLVD
Volt”, or the discharge time is longer
than the “BLVD Time”, the BLVD
contactor will be open automatically
2. BLVD through manual operation
Critical 4
BLVD
enabled
23
Load 1 Faiure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical 6
24
Load 2 Faiure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical 6
25
Load 3 Faiure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical 6
26
Load 4 Faiure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical 6
27
Load 5 Faiure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical 6
28
Load 6 Faiure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical 6
29
Load 7 Faiure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical 6
30
Load 8 Faiure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical 6
31
Load 9 Faiure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical 6
32
Aux Load Fails
The last route faulty
Critical
6
33 Batt1
Failure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical None
34 Batt2
Failure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical None
35 Batt3
Failure
Over-load, short circuit, manual
disconnection or alarm circuit faulty
Critical None