Chapter 7  “1+N” System      55 
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA    User Manual 
8. Check that no warning message is displayed in the top right corner of the LCD screen and the status of the LEDs 
as follows: 
Table 7-1    LED status 
LED 
Status 
Rectifier LED 
Steady green 
Bypass LED 
Off 
Battery LED 
Off 
Inverter LED 
Steady green 
Load LED 
Steady green 
Alarm LED 
Off 
 
7.3.5   Shutdown Procedure (Complete UPS And Load Shutdown) 
Refer to 5.7    Shutdown Procedure (Complete UPS And Load Shutdown)
7.4   Dual Bus System Installation Procedures 
7.4.1   Cabinet Installation 
As shown in Figure 7-3, the dual bus system consists of two independent UPS configurations each consisting of one 
or more UPS modules. Dual bus systems are high availability configurations suitable for loads with multiple input 
terminals. For single input loads an optional static transfer switch (STS) may be added. 
The objective of the dual bus system is to keep the output of two independent UPS systems (or parallel systems) in 
synchronization using optional load bus synchronization (LBS) cable. One system is designated as the master; the 
other is designated as the slave. The operating modes covered comprise master and or slave operating inverter or 
bypass mode. 
In installation, place the UPS modules side by side and interconnect as described in the following sections.     
制电缆
Bypass supply
Input rectifier
Input rectifier
Parallel
cable
LBS
cable
Parallel
cable
Load
Bypass supply
Input rectifier
Input rectifier
 
Figure 7-3    Typical dual bus system (using STS and LBS cable) 
7.4.2   Protective Devices 
Refer to 3.1.6  Protective Devices.